A change of use is often decided without thinking about the structure: a ground-floor flat becomes a shop, an office floor becomes an archive. Yet SIA 261 sets different imposed loads depending on how the rooms are used, and a beam sufficient for housing may no longer be sufficient for a shop or for storage.
The Site structural design studio offers categories A housing, B offices, C assembly areas, D shopping areas and E storage, with default imposed loads of 2, 3, 4, 5 and 5 kN/m² and the related combination factors ψ. These are adjustable defaults, to be checked in SIA 261 (storage loads depend heavily on what is stored). The result is a preliminary design that does not replace the calculation note signed by a civil engineer (SIA 260 to 267).
Worked example: 5.00 m floor beam by category of use
Main beam of a 20 cm reinforced concrete floor with screed (6.5 kN/m², default value of the studio), span 5.00 m, tributary width 4.00 m. ULS combination 1.35 · g + 1.5 · q. Default imposed loads of the studio. Hand calculation to understand the result.
| Category | q_k (kN/m²) | Load q_Ed (kN/m) | Moment M_Ed (kN·m) |
|---|---|---|---|
| A: housing | 2 | 47.1 | 147.2 |
| B: offices | 3 | 53.1 | 165.9 |
| C: assembly areas | 4 | 59.1 | 184.7 |
| D: shopping areas | 5 | 65.1 | 203.4 |
| E: storage | 5 | 65.1 | 203.4 |
The permanent load per metre of beam is 6.5 × 4.00 = 26.0 kN/m; the imposed load 3 × 4.00 = 12.0 kN/m for offices. The design load is 1.35 × 26.0 + 1.5 × 12.0 = 35.1 + 18.0 = 53.1 kN/m, and the moment 53.1 × 5.00² / 8 = 165.9 kN·m. For a shop, the imposed load rises to 20.0 kN/m: 35.1 + 30.0 = 65.1 kN/m and 203.4 kN·m, that is 22.6 % more.
Categories D and E have the same default imposed load, and therefore the same ULS moment; but for storage the studio applies a higher quasi-permanent factor (0.8 instead of 0.6), which increases the long-term deflection and the mass used for the vibration criterion. In the tender for an alteration, this calculation justifies strengthening or a heavier section; the actual imposed load is set with the engineer according to the planned use.
Changing from offices to a shop raises the design moment from 165.9 to 203.4 kN·m (+22.6 %) on this 5.00 m beam: a change of use is checked before the works.
3 frequent mistakes with categories of use
Keeping the original category after a change of use
A housing floor turned into a shop or a meeting room must be checked with the new category, even if nothing changes in the construction itself.
Treating storage as a fixed value
Archives, shelving or pallets can far exceed the default value. The storage load is set according to what is actually stored.
Forgetting partitions and finishes
A new fit-out often adds partitions, suspended ceilings and heavier floors. These are permanent loads to add to the slab.
Comparing categories of use in 3 steps
- Describe the floor
In the floor beam mode, enter the span, the tributary width and the slab type or its real permanent load. - Choose the category
Select A, B, C, D or E; adjust the imposed load if the engineer or the planned use requires it. - Compare and export
Note the section chosen, the utilisation, the deflection and the frequency for each category; export the sheet for the alteration file.
What the free version does not do for a change of use
The imposed loads and the factors ψ are defaults that have not been checked against SIA 261. The studio only checks a beam on two supports, without the slab, the columns, the foundations or the fire protection required by the new use. It is a decision aid that replaces neither the calculation note signed by a civil engineer nor the permit for the change of use. For a timber joist or beam, see the page on C24 and GL24h joists.
Soumissions prices the strengthening and the alteration works; the ERP tracks the site and the invoicing; Portail chantier shares the sheet and the supporting documents with the client.
Frequently asked questions
What imposed load for a dwelling?
The studio starts from 2 kN/m² for category A housing. The value to use is the one in SIA 261, to be checked by the engineer.
Is an office more heavily loaded than a dwelling?
Yes, the studio starts from 3 kN/m² for offices against 2 kN/m² for housing. An existing beam may therefore need strengthening.
Why does storage change the deflection but not the moment?
With the default values, D and E have the same imposed load, but a larger share of the storage load is treated as long-lasting: the long-term deflection increases.
Is the studio enough for a change of use?
No: it helps estimate the effect on one beam. The full check of the structure and the permit application still have to be done.