🧱 CFC 238Structured copper cabling: classes, installation and linksChapter 1 of 10 in the section

Cat 5e, Cat 6A or Cat 7: what really changes on a construction site

This chapter details the actual selection criteria between Cat 6A and Cat 7 copper cables on Swiss construction sites. You will learn to assess the impact of F/FTP and S/FTP shielding designs, adhere to permanent link limits under current standards, and quantify the technical risks of an undersized network infrastructure.

Key takeaways

  • Standard ISO/IEC 11801 sets the absolute permanent link limit at 90 metres with no exceptions.
  • The RJ45 connector mechanically limits the actual performance of Cat 7 cables to Class EA.
  • The S/FTP design offers superior electromagnetic immunity compared to F/FTP in dense commercial environments.
  • Replacing embedded copper cabling generates prohibitive rework costs for the client.

Twisted-pair performance and ISO/IEC 11801 normative constraints

Choosing a copper medium for universal communication cabling is not based on theoretical speeds of active equipment, but on certified bandwidth and resistance to disturbances in the installation environment. Standard ISO/IEC 11801 classifies links by component categories and overall performance classes for the full channel. Category 6A (Class EA) guarantees an operating frequency up to 500 MHz, which is sufficient for the 10GBASE-T protocol over the maximum standardised distance. Category 7 (Class F), rated up to 600 MHz, provides superior crosstalk headroom, but faces a hardware constraint in Swiss practice: the legacy standardised RJ45 interface no longer meets transmission criteria beyond 500 MHz. Using specific non-RJ45 connectivity for Class F requires costly patch cords and restricts patch panel modularity.

Permanent link
Fixed portion of the horizontal structured cabling link, measured between the office telecommunications outlet and the patch panel female connector in the telecommunications room, excluding patch cords.

Regardless of the cable category selected, the dimensional rule remains unchanged: the maximum length of the permanent link is capped at 90 metres. The overall transmission channel allows 10 metres of flexible patch cords distributed between the patch panel and the work area to reach the 100-metre ceiling. Cat 7 cables have a larger outer diameter and a slightly larger copper cross-section (AWG 23), which reduces linear attenuation. However, this physical property grants no extra length allowance: a cable certifier calibrated to standard ISO/IEC 11801 will automatically fail the time-domain reflectometry test beyond this 90-metre boundary, regardless of the observed margin on insertion loss or near-end crosstalk.

Technical comparison of Cat 6A and Cat 7 horizontal links
Technical characteristicCategory 6A (Class EA)Category 7 (Class F)
Maximum certified frequency500 MHz600 MHz
Standard termination connectorShielded RJ45 (Keystone)Proprietary dedicated connectors or RJ45 restricted to Class EA
Common shielding types in SwitzerlandF/UTP, U/FTP, F/FTPS/FTP mandatory
Average cable outer diameter7.0 to 7.5 mm7.5 to 8.5 mm
Minimum bending radius during installation8 times the outer diameter8 times the outer diameter

Shielding management is the second decisive factor. Two constructions dominate Swiss tenders: F/FTP shielding and S/FTP shielding. F/FTP (Foiled with Foiled Twisted Pairs) cable features an aluminium foil around each individual pair as well as an overall foil wrapping the bundle under the outer jacket. This solution offers excellent protection against alien crosstalk while maintaining good flexibility when pulling through M20 or M25 conduits. S/FTP (Shielded with Foiled Twisted Pairs) cable combines individually shielded pairs with an overall tinned copper braid. This braid ensures very low transfer impedance continuity, which is essential in service shafts where extra-low voltage cables run alongside industrial interference sources or inverter power supplies. The downside to this robustness: increased linear weight, cable stiffness, and a demanding bending radius that quickly fills the usable capacity of cable trays and back boxes.

Installation trade-offs and anticipating long-term obsolescence

Installing a copper infrastructure is planned around a technical depreciation cycle of ten to fifteen years. Over this period, active equipment, high-speed wireless access points, and PoE-powered equipment (Power over Ethernet up to 90 W) will evolve. Selecting Cat 7 cable with Cat 6A connectors is a common practice among electrical planners in French-speaking Switzerland: it establishes a physical backbone impervious to thermal ageing caused by intensive PoE, while preserving the full interoperability provided by RJ45. This hybrid approach ensures a high noise margin and prepares the network for future standards without penalising immediate costs for connection modules.

Undersizing the horizontal infrastructure to cut initial costs is a major miscalculation. Installing Cat 5e or standard unshielded Cat 6 (U/UTP) leads the client into a rapid technical dead end given modern network requirements. The cost of reworking an undersized cabling system far exceeds the modest extra material cost incurred during the structural work phase. In an occupied commercial building, replacement involves substantial resources: removing suspended ceilings, extracting congested cable bundles, restoring fire-rated wall penetrations, complex pulling through partially crushed conduits, and completely reorganising floor distribution frames. The costs generated by operational downtime and finishing work labour routinely reach three to five times the cost of cabling correctly sized at the outset (refer to /soumissions/ for rework cost analysis).

If the material supplied by the client or the site designated by them is found to be defective, or if any other circumstance jeopardises the proper or timely execution of the work, the contractor shall immediately inform the client, failing which they shall bear the consequences.

art. 365 CO al. 3

The professional duty to notify requires telecommunications installers to alert their client regarding the durability of the work. Pursuant to art. 365 CO al. 3, the installer flags any technical directive that jeopardises the future usability of the network, particularly selecting a medium incapable of withstanding the heat rise caused by modern PoE protocols or causing transmission errors through a lack of shielding. The rational trade-off consists of specifying at least Cat 6A F/FTP cable for standard offices, or Cat 7 S/FTP for mixed environments, thereby guaranteeing a full lifecycle for the installation without premature rework.

Installation geometry and shield behaviour: physical constraints of F/FTP versus S/FTP

On the construction site, choosing between a Category 6A infrastructure and a Category 7 installation is not based on a marketing claim of theoretical bandwidth. Practical constraints depend primarily on cable mechanics, shielding behaviour under electromagnetic interference, and strict compliance with standard ISO/IEC 11801.

Standard ISO/IEC 11801 sets a maximum length of 90 metres for the horizontal permanent link, supplemented by a total of 10 metres of patch cords to form the complete 100-metre channel. Although this distance limit is identical for Cat 6A and Cat 7, the safety margin against insertion loss (attenuation) varies significantly at higher frequencies. Category 7 cable often features a heavier conductor gauge (AWG 23 or even AWG 22), which reduces heating during high-power PoE applications, but increases the outer diameter and rigidity of the bundle.

Technical comparison and site installation constraints based on shield design
Site characteristicCat 6A F/FTP cableCat 7 S/FTP cable
Shield constructionAluminium foil per pair + overall aluminium foilAluminium foil per pair + overall tinned copper braid
Average outer diameter7.0 to 7.6 mm7.8 to 8.6 mm
Dynamic bending radius (pulling)8 x outer diameter (approx. 60 mm)8 x outer diameter (approx. 70 mm)
Static bending radius (installed)4 x outer diameter (approx. 30 mm)4 x outer diameter (approx. 35 mm)
Mechanical tensile strengthModerate (risk of tearing the overall foil)High (braid absorbs mechanical load)
Connecting the shield to the connectorDrain wire or direct contact on foil360° braid flaring and fold-back

F/FTP (Foiled with Foiled Twisted Pair) shielding uses aluminium foil over each pair along with an overall aluminium foil. It maintains a compact footprint and is ideally suited for dado trunking and standard embedded conduits of 25 or 32 mm diameter. Conversely, S/FTP (Shielded with Foiled Twisted Pair) shielding, the standard for Category 7, replaces the overall foil with a metallic braid. This braid provides excellent shielding attenuation against industrial interference, but significantly adds weight to cable trays and increases pulling resistance around tight bends.

Operational trade-off: initial surcharge versus reworking obsolete cabling

The economic calculation of a multimedia or commercial infrastructure does not end with the purchase price of the cable drum. While the raw supply cost difference between Cat 6A F/FTP and Cat 7 S/FTP cable remains moderate (often between 20% and 35% on bare copper linear metre prices), the financial impact of underestimating the permanent link proves disproportionate during the subsequent operating phases of the building.

In office buildings, retail premises, or luxury residential units, the cost of fully replacing data cabling bears no comparison with the initial investment. Replacing copper cabling ten years after handover entails:

  • Removing and refitting metallic or mineral suspended ceilings, with subsequent painting touch-ups.
  • Opening, traversing, and fire-stopping compartment wall penetrations.
  • Carrying out works in occupied premises, requiring out-of-hours shifts and dust protection measures.
  • The risk of overcrowding risers and embedded conduits if the new cable diameter exceeds the original spare capacity.
  • Completely recreating labelling, patching diagrams, and channel-by-channel certification reports.

On a Swiss construction site, the cost of reworking undersized cabling routinely reaches five to eight times the price of the original new installation, primarily due to the finishing work labour required to regain access to pathways. The contractor fulfils the general duties of care under art. 364 CO by directing the client towards a durable solution right from tender award.

Managing test non-conformities and link performance disputes

On-site, detecting a permanent link rejected by the cable certifier initiates a strict technical troubleshooting sequence before any commercial dispute. When the tester indicates a failure in alien crosstalk, return loss, or attenuation, the site supervisor first verifies calibration compliance with measuring adapters meeting standard ISO/IEC 11801. A pinched bending radius at a trunking exit or excessive pair untwisting during modular jack termination is enough to degrade a copper link that passed laboratory tests.

If the fault stems from physically exceeding the maximum permanent link length set at 90 metres by the electrical engineer, no software adjustment is possible. Pursuant to art. 365 al. 3 CO, the contractor immediately informs the client if any circumstance jeopardises the proper execution of the work. The telecommunications installer sends written notification to site management as soon as the on-site measurement is taken, recommending the installation of an intermediate floor distributor or transitioning the terminal link to a fibre optic backbone.

If the shielding is damaged due to excessive pulling tension during installation—particularly on an F/FTP jacket where the aluminium foil tears more readily than the braid of an S/FTP cable—screen continuity is compromised. This break immediately degrades the required electromagnetic immunity. The site foreman records time-domain reflectometry traces in the self-inspection report, locates the crushed section in the cable trays, and completely pulls a new replacement bundle before suspended ceilings are closed permanently.

Frequently asked questions

Can a Cat 7 permanent link terminated with standard RJ45 connectors be certified?

No. Standard ISO/IEC 11801 stipulates that channel performance aligns with the weakest component. The RJ45 modular connector is physically limited to Cat 6A requirements (500 MHz frequency). A Cat 7 cable terminated with RJ45 will systematically be tested and certified against Class EA permanent link limits, without gaining the transmission specifications of Class F at 600 MHz.

What is the absolute maximum length for a copper permanent link?

The maximum permanent link length is set at 90 metres by structured cabling standards, for both Cat 6A and Cat 7. This allows the addition of two 5-metre patch cords at the ends to complete the 100-metre total transmission channel. Beyond this metric limit, attenuation issues prevent compliant sign-off during acceptance testing.

Why prefer S/FTP shielding over F/FTP in major refurbishments?

S/FTP cable features an overall tinned copper braid enclosing foil-shielded pairs, whereas F/FTP relies solely on an outer aluminium foil. In refurbishment projects, cable-pulling through congested conduits or tortuous routes subjects the jacket to high tensile forces. The metallic braid of S/FTP absorbs mechanical strain without compromising electromagnetic shielding continuity.

What is the actual financial risk of reworking an undersized network?

The cost of replacing cabling is primarily absorbed by stripping-out labour, suspended ceiling removal, and facility downtime. Reworking an undersized installation ten years after construction typically costs three to five times the original investment. Installing shielded Cat 6A from the outset safeguards the physical infrastructure for future generations of active equipment.

Texts and standards cited

  • ISO/IEC 11801Information technology - Generic cabling systems for customer premises
  • CO art. art. 365 COMaterials and site conditions: the contractor is liable for the sound quality of materials supplied; if any circumstance jeopardises the proper or timely execution of the work, they shall immediately inform the client