Heat demand and sizing of the heat generation: the execution reference

This section is aimed at heating installers, team leaders and site foremen who deal with the sizing of heat generation. It provides concrete methods for calculating the actual heat losses without an arbitrary safety margin, including domestic hot water loads, meeting the cantonal requirements derived from the MoPEC and selecting the right hydraulic regime to avoid premature compressor wear and drifting energy consumption.

  • 10chapters
  • 22 000words
  • 6sections in the training course
  • 60chapters in total

Key values to remember 4

norme SIA 384/1

-8 to -12

Average outdoor design temperature on the Swiss Plateau

norme SIA 384/1

35

Maximum flow temperature for a standard underfloor heating network

Swiss professional recommendations of the industry

12

Recommended minimum water volume for a variable-speed heat pump

MoPEC

10

Minimum share of renewable energy often required on replacement

Technical scope of sizing and construction site interfaces

Sizing a heat generation system is the founding technical act of the heating installer under CFC 241. Determining the required output does not mean copying the rating plate of an old boiler or stacking up reserve factors as a precaution. The aim is to match the installed output strictly to the actual heat losses of the building envelope and the actual reheating needs, calculated in accordance with the provisions of SIA 384/1.

The calculation covers domestic hot water solely in terms of its heat exchange output or storage volume, without encroaching on the sizing of the sanitary distribution loops or the taps and fittings, which fall under the CFC 250 trade. Likewise, the air-handling aspects of air treatment installations belong to CFC 244, and fine control via field bus to the CFC 238 electrical installers.

Division of tasks and scope limits in the boiler room
Component or serviceResponsible tradeCFC 241 scope limit
Heat generator and buffer tankCFC 241 (Heating)Supply, hydraulic connection and thermal commissioning
Power supply and isolationCFC 232 (Electrical)Connection to the terminals of the generator control cabinet
Drinking water circuit and DHW recirculationCFC 250 (Sanitary)Connection to the flanges or primary sockets of the sanitary heat exchanger
Combustion air supply and forced ventilationCFC 244 (Ventilation) / CFC 241Sizing of free cross-sections according to the VKF/AEAI fire safety directives
Floor heat-up protocolCFC 241 (control) / CFC 281 (screed)Management of the water temperature steps, with no responsibility for the drying of the mass

Contractually and legally, the contractor remains responsible for the works he calculates and installs. Under art. 365 CO, if the input data supplied by the client or the historical consumption records are incomplete or clearly disproportionate, the installer is obliged to inform his principal immediately in order to be relieved of liability in the event of underperformance or a dispute over the seasonal efficiency.

Methodical path: from heat load to real-life operation

The design and execution of a high-performance heating installation require a rigorous sequential approach. The ten chapters of this section detail each operational step, from the theoretical thermal determination to checking the behaviour of the installation during the first months of heating.

  1. Step 1: Assessment of the fundamental loadsChapters [J1-01] to [J1-04] deal with building physics. Heat losses are calculated according to SIA 384/1, oversizing that causes short cycling is tracked down, operating temperatures are lowered to maximise heat pump efficiency, and domestic hot water preparation is included without overestimating the peak output.
  2. Step 2: Legal framework and spatial integrationChapters [J1-05] and [J1-06] cover the replacement of installations in accordance with the requirements of the cantonal legislation derived from the Model Energy Provisions of the Cantons (MoPEC). They also define the safety constraints for technical rooms: minimum volumes, air supplies and necessary clearances.
  3. Step 3: Hydraulic diagram and buffer componentsChapters [J1-07] and [J1-08] address the choice of the bivalence point for heat pumps and the integration of the buffer volume. The aim is to guarantee the minimum flow rates without creating parasitic thermal mixing that would destroy the coefficient of performance of the installation.
  4. Step 4: Site management and post-commissioning optimisationChapters [J1-09] and [J1-10] complete the practical implementation. Heating is maintained in occupied buildings during the winter construction site, then the heating curves are adjusted on the basis of the heat meters during the first operating season.

Rigour applied from the preliminary design stage avoids common drifts: a buffer tank connected in full decoupling without thinking about flow rates, a boiler output doubled out of habit, or factory settings never corrected. Every technical choice affects the profitability of the installation over more than twenty years.

📘 Chapters in this section 10

Heat demand and sizing of the heat generation

Calculating the required output: heat losses, design temperature and heat gains

Determine the exact heat load of the building according to the standard without applying unjustified excess output.

Heat demand and sizing of the heat generation

Too big costs more: short cycling, wear and reduced comfort

Find out why an oversized generator destroys its compressor and wastes energy in the mid-season.

Heat demand and sizing of the heat generation

Choosing the operating regime: flow temperature, temperature difference and the consequences for everything else

Lower the water temperatures of your networks to multiply the coefficient of performance of the installations.

Heat demand and sizing of the heat generation

Hot water as a load: reheat capacity, priority and storage cylinder

Manage hot water production by hydraulic priority without doubling the installed heating output.

Heat demand and sizing of the heat generation

Replacing a boiler today: cantonal requirements and the file to compile

Master the cantonal energy forms and the mandatory supporting documents to validate your conversion applications.

Heat demand and sizing of the heat generation

The room: volume, air supply, clearances and exit door

Check the combustion air cross-sections, the maintenance distances and the secure access in the boiler room.

Heat demand and sizing of the heat generation

Back-up heating: bivalence point, resistance heater hours and winter bill

Calculate the bivalence temperature precisely to limit the switching on of the backup electric heating elements.

Heat demand and sizing of the heat generation

The buffer volume: what it is for, when it is unnecessary, how to connect it

Select the right buffer tank connection to ensure the flow rates without degrading the temperatures.

Heat demand and sizing of the heat generation

Changing the heat production in winter: temporary supply, shutdown and tenant information

Install temporary mobile boiler rooms and secure the heat supply to occupants during winter works.

Heat demand and sizing of the heat generation

Checking after the event: meters, first-season readings and curve correction

Adjust the control curve slope after the first cold spells using the energy meter readings.