Membranes: bitumen, synthetic, laying and jointing: execution standard

Aimed at team leaders, site foremen and waterproofing site managers, this section deals exclusively with the installation of the waterproofing layer on flat roofs and terraces. It details the rigorous choice between elastomer bitumen and synthetic, overlap geometry, torch-on or hot-air welding execution, fastening methods, and the systematic inspections required by standard SIA 271.

  • 10chapters
  • 22 000words
  • 6sections in the training course
  • 60chapters in total

Key values to remember 5

norme SIA 271

80 mm

Minimum longitudinal overlap for welded bituminous membrane

norme SIA 271

100 mm

Minimum end lap (transverse) for bituminous membrane

norme SIA 271

50 mm

Minimum overlap for hot-air welded synthetic membrane

norme SIA 271

80 kg/m²

Minimum surface mass of gravel (16/32 mm) for standard 50 mm ballast

OTConst art. 41

2 m

Fall height requiring fall-protection measures at roof edge

Technical scope and work limits

This section brings together all Swiss codes of practice applicable to the installation of waterproofing membranes on flat roofs, terraces, balconies, and underground car park roofs. It sets out laying techniques for two-ply elastomeric bitumen (SBS) systems, single-ply bitumen, as well as thermoplastic (FPO, PVC) or elastomeric (EPDM) synthetic membranes. Jointing methods by thermal welding, bonding, or mechanical fastening are covered exclusively from the perspective of standard SIA 271 requirements.

The waterproofer's responsibility begins upon handover of the substrate (concrete, profiled steel deck, timber panels, or thermal insulation) and ends with the delivery of a watertight, protected envelope. The application of occupational safety regulations, particularly the prevention of falls from height when working near unguarded edges, is mandatory under art. 41 OTConst as soon as the fall height exceeds 2 metres.

Classification of membrane families and bonding methods according to SIA 271
Membrane familyMain bonding methodPrimary area of useSheet jointing
Elastomeric bitumen (SBS)Fully torched or semi-independentTrafficable terraces, inverted roofs, car parksTorch-welding or hot bitumen
Flexible polyolefin (FPO/TPO)Mechanical fastening or loose-laid ballastedLarge industrial surfaces, lightweight roofsAutomated or manual hot-air welding
Polyvinyl chloride (PVC-P)Mechanical fastening or bondingNon-accessible exposed roofs, light refurbishmentsHot-air thermal welding
Ethylene propylene diene monomer (EPDM)Cold bonding or loose-laid ballastedGreen roofs, temporary stormwater retentionSplicing adhesive tape or vulcanisation

Execution sequence: from preparation to remedial works

To ensure the durability of a waterproofing system, the laying team must approach operations in a rigorous technical order. An assembly error or the wrong choice of system leads to major failures in the thermal insulation and building structure, often undetectable before the first water test.

  1. Membrane selection and mechanical designDetermine the type of membrane based on roof use, exposure class, and load constraints, then calculate the fastening layout pattern to resist wind uplift.
  2. Jointing, welding, and destructive or non-destructive testingExecute longitudinal and transverse overlaps. Set heating temperatures, carry out the morning peel test, and inspect every centimetre of the seam using a seam probe.
  3. Installation of connections and detail waterproofingAdapt the laying method using bonding or ballasting depending on main areas and perimeter edges. Detail complex penetrations and upstands using a reinforced liquid waterproofing system.
  4. Construction site protection and corrective maintenanceProtect the surface against damage from other trades, control wheeled loads, and execute compliant repairs using bridging strips and welded waterproofing patches.

📘 Chapters in this section 10

Membranes: bitumen, synthetic, laying and jointing

Elastomeric bitumen or synthetic membrane: what decides the choice

Select the appropriate system for the building's load, thermal movement, and operational requirements.

Membranes: bitumen, synthetic, laying and jointing

Membrane welding: lap width and seam probe inspection

Master overlap widths and the systematic technique for detecting unbonded seams.

Membranes: bitumen, synthetic, laying and jointing

Hot-air welding: temperature, speed and peel test

Configure the nozzle, travel speed, and verify seam strength with the daily peel test.

Membranes: bitumen, synthetic, laying and jointing

Mechanically fastened membrane: layout of sheets and wind uplift resistance

Distribute fastenings across perimeters and central zones to counteract wind uplift pressures.

Membranes: bitumen, synthetic, laying and jointing

Bonded waterproofing: primer, flash-off time and adhesion achieved

Prevent debonding by checking solvent evaporation and proper saturation of bonding primers.

Membranes: bitumen, synthetic, laying and jointing

Loose-laid ballasted systems: ballast mass, grading and perimeter zones

Calculate the gravel ballast required to stabilise the system without overloading the structure.

Membranes: bitumen, synthetic, laying and jointing

Laying in cold or damp weather: limit temperatures and morning dew

Anticipate the dew point and ensure safe preheating of substrates at sub-zero temperatures.

Membranes: bitumen, synthetic, laying and jointing

Liquid waterproofing: reinforcement, thickness and critical detailing points

Seamlessly terminate inaccessible upstands and through-pipes using reinforced resin.

Membranes: bitumen, synthetic, laying and jointing

Protecting the membrane from other trades: traffic, scaffolding and tools

Install temporary protection walkways to safeguard the waterproofing against damage by other trades.

Membranes: bitumen, synthetic, laying and jointing

Repairing a membrane: substrate preparation, patch, and durable weld

Decontaminate the aged substrate and apply chamfered reinforcement patches for a fully watertight repair.