🧱 CFC 226Upstands and special detailingChapter 10 of 10 in the section

Free edge: edge trim, drip edge and façade protection

This chapter guides you through the installation of a watertight and durable free edge without a parapet wall. You will learn how to fit a suitable metal trim, set the geometry of the drip edge to protect façades from staining over the long term, dimension mechanical fixings against wind suction, and join waterproofing sheets in accordance with Swiss trade standards.

Key takeaways

  • The drip edge sheds runoff water away to prevent muddy streaks on the façade cladding.
  • The mechanical fixing of the edge trim must withstand high wind suction forces.
  • Laminated metal sheet allows direct, homogeneous welding of the waterproofing membrane onto the edge.
  • An expansion gap between successive trims prevents creasing and tearing of the waterproofing assembly.

Trim geometry and water shedding to preserve the façade

On a flat roof without a parapet wall, the free edge delimits the waterproofed surface while ensuring controlled discharge or retention of surface water. Without a rigid metal edge fitted with a clean drip edge, rainwater laden with atmospheric dust runs down the exterior downstand. Water infiltrates beneath soffits, deteriorates mineral renders through freeze-thaw cycles, and causes indelible dark streaks on rendered façades or ventilated external wall insulation.

Free edge drip edge
Lower metal fold of an edge sheet forming an acute angle outwards, designed to force runoff water droplets to break away by gravity before reaching the face of the façade.

The edge trim performs a dual function: it forms a clean stop for the waterproofing layer and throws water sufficiently far from the vertical structure. Trade standards require a water throw that depends directly on the height of the building. The greater the downstand, the further the drip edge must project beyond the finished face of the façade to counter the effects of downward wind eddies.

Geometric requirements for edge trims according to façade configuration
Downstand height of the trimMinimum clearance to the finished faceMinimum fall of the horizontal legMain risk in case of insufficient clearance
Less than 100 mm20 mm2% inwardsInfiltration beneath the fascia by capillary action
100 to 250 mm30 mm2% inwardsRegular vertical staining from runoff washing
Greater than 250 mm40 mm3% inwardsThermal debonding and greasy streaks

The upper surface of the trim must feature an inward fall towards the roof to prevent residual water from ponding on the metal and spilling over the façade during light rain. For roofs without a perimeter collecting gutter, a trim with a raised upper lip forms a low upstand, retaining wash water on the waterproofing assembly until it reaches the rainwater outlets.

Mechanical fixing against wind and watertight membrane bridging

Free edges are the roof zones most exposed to wind turbulence and suction. Local uplift can tear away an improperly anchored trim, triggering progressive peeling of the adjacent waterproofing. Fixing the edge trim requires a rigid substrate, typically a treated timber edge board or a solid wood packer mechanically fixed to the concrete structural work, level with the thermal insulation.

  1. Alignment and packing of the substrateFix the edge timber or metal upstand to the structural work. Align using a chalk line to accommodate concrete tolerances and ensure a perfectly straight downstand on the façade.
  2. Installation of trims and expansion managementPosition the lengths of trims leaving a 5 mm gap between each 2 to 3-metre section. Insert metal joint connecting clips beneath the joint to ensure alignment without restricting thermal contraction.
  3. Reinforced mechanical fixingAnchor the sheet metal using large-head stainless steel screws, spaced at a maximum of 150 to 200 mm, staggered along the horizontal flange. On masonry substrates, use appropriate hammer-in fixings.
  4. Welding of the waterproofing membraneOn laminated metal sheet, hot-air weld the synthetic waterproofing sheet directly onto the degreased horizontal flange. For bituminous membranes, install a bridging perimeter strip torched with elastomeric bitumen after applying a bonding primer.

The waterproofing layer bond onto the horizontal flange must be at least 100 mm wide to ensure adhesion under wind uplift forces. With two-layer bituminous waterproofing, the base layer is dressed beneath the trim, while the cap sheet covers the metal flange up to the inner corner of the drip edge, ensuring complete continuity without any risk of wind-driven water infiltration.

Trim joints, corners and continuity of water shedding

The absence of a parapet wall concentrates thermal and mechanical stresses along the free edge perimeter. Metal edge trims undergo significant dimensional variations under the effect of solar radiation and frost. Without strict management of butt joints and corner pieces, expansion disrupts the continuity of the drip edge or tears the waterproofing bridging strips. The immediate result is localized streaking on render or cladding, quickly followed by infiltration beneath the insulation assembly.

Expansion joint clip
An intermediate metal piece slid or clipped at the joint between two lengths of edge trim, ensuring mechanical alignment while accommodating expansion and contraction movements without jamming the drip edges.

Each length of folded sheet metal or extruded aluminium trim must be installed with a clear gap at the butt joint. Mechanical fixing must never restrict free sliding at the connections. An internal joint clip bridges the drip edge to prevent water drawn by capillary action from breaching the gap and wetting the slab edge or façade panel.

Execution of joints and corners on free edges
Specific detailRequired technical measureMembrane connectionRisk in case of non-compliance
Butt joint on running lengthsGap of at least 5 mm with underlying metal joint clipLoose unbonded tape beneath the bituminous or synthetic bridging stripCreasing or shearing of the waterproofing during hot weather
External cornerFactory preformed mitred and welded single-piece corner, minimum leg length 250 mmPreformed corner gusset heat-welded or bonded with full continuityInfiltration beneath the façade corner and mechanical tear-off by wind
Internal cornerPrefabricated corner with fitted drip edge ensuring uninterrupted water detachmentUnderlying waterproofing reinforcement and reinforced plastomeric or elastomeric bridgingConcentration of runoff water and heavy staining of the vertical cladding
Termination against an upstandEdge plates dressed vertically and sealed with compatible masticIndependent waterproofing upstand connected at the code-compliant heightDirty water runoff bypassing the edge trim and penetrating the façade insulation

Connecting the membrane to the metal trim demands flawless surface preparation. On mill-finish aluminium or galvanized steel, preliminary application of a reactive primer ensures the adhesion of the bridging layer. Laminated metal trims allow direct, homogeneous welding of the synthetic waterproofing membrane. In this case, the weld seam must be firmly pressed along the edge to prevent any water ingress under wind pressure.

Façade protection, drip clearance and interface coordination

The core purpose of the drip edge is to mechanically detach water droplets from the external face of the wall. Along flat roof edges, aerodynamic turbulence tends to drive liquid streams against the cladding. The edge trim must project sufficiently to compensate for these deflections and prevent runoff down the wall, which degrades mineral renders and fosters algae and mould growth.

This minimum horizontal clearance of 20 mm must be measured relative to the finished façade, meaning inclusive of the thickness of render, ventilated cladding boards or external wall insulation. The vertical downstand of the drip edge below the edge of the structural work must extend low enough to conceal the upper thermal break and create a clean capillary break.

  1. Façade thickness checkMeasure the overall thickness of the façade system specified in the project drawings to confirm the overhang of the trim's horizontal flange before installation.
  2. Installation of the thermal packerInsert an insulating batten or rot-proof timber along the slab edge to eliminate the thermal bridge and provide a rigid anchoring substrate.
  3. Fixing and fall checkFix the trim with a slight inward fall of 2% towards the roof to prevent standing water from spilling over the outer edge.
  4. Membrane clamping and thermal bridgingApply the bridging strip, ensuring a complete watertight lap onto the degreased sheet metal and onto the main roof membrane.
  5. Drip clearance inspectionVisually check the uniformity of the drip fold and confirm the total absence of direct contact with the render or cladding panels.

On construction sites with significant height hazards, planning the waterproofer's operations along roof edges must integrate collective edge protection. In accordance with art. 23 OTConst, perimeter edge protection must be installed in unprotected locations where the fall height exceeds 2 m. Free edge work requires immediate coordination with scaffolding erectors to maintain the safety net beyond the drip edge without hindering the installation of the metal apron.

Management of edge failures, drip defects and remediation protocol

A defective free edge immediately exposes the structure to two major risks: direct runoff over the façade cladding and assembly uplift under wind gusts. Failures typically occur following severe wind events or prolonged driving rain. Faced with a torn trim, a delaminated membrane, or persistent staining along the roof perimeter, the intervention team applies a rigorous methodology to secure the perimeter, identify the root cause of the defect, and repair the detail without compromising the adjacent main roof waterproofing.

  1. Defect diagnosis and mechanical inspectionCheck the pull-out resistance of the remaining screws or fixings along the edge line. Verify whether the substrate (concrete, timber, or masonry) shows crumbling or rot. Measure the projection of the drip edge relative to the render or cladding to assess the water droplet path.
  2. Assembly stripping and membrane cuttingNeatly cut the waterproof membrane using a hook-blade utility knife 150 mm back from the trim's fixing flange. Remove twisted, torn or improperly clipped trims. Clean and clear all dust from the installation area down to the load-bearing substrate.
  3. Substrate repair and reinforced anchoringReplace damaged packing battens or edge boards. Fix the new extruded or folded metal trim following a staggered fixing pattern every 200 mm. Leave a 5 mm expansion gap between each 3 m section fitted with a joint clip.
  4. Watertight bridging and thermal closureApply a suitable bonding primer onto the degreased metal flange. Weld or bond a bridging strip compatible with the main roof membrane, maintaining a minimum cross-lap of 100 mm beyond the cut line.

When defects stem from a design or execution flaw that has caused damage to the façade render, disputes are common. Under CO, the client may demand the rectification of the defective work at the contractor's expense. Careful execution of the drip edge and expansion clipping prevents these costly disputes.

Frequently asked questions

How should thermal expansion between two free edge trims be accommodated?

Thermal movements require a 5 mm gap between each three-metre section. This gap accommodates the linear expansion of aluminium or zinc. To prevent infiltration, a metal joint clip is clipped or slid beneath the trims, forming a mechanical watertight joint under the membrane bridging strip.

What is the minimum drip edge projection required relative to the façade?

Water droplets forming under the drip lip must fall freely without running down the wall. A minimum clearance of 20 mm between the downstand edge of the trim and the finished face of the façade or render is essential. Below this distance, dirty roof runoff runs down the exterior finish.

Why does bituminous membrane often peel off the metal trim flange?

This failure results from failing to degrease bare metal or omitting the bituminous primer before torching. Smooth mill-finish aluminium or galvanized steel offers no direct mechanical key for hot bitumen. Applying a solvent-based primer and uniformly heating the bridging strip ensure long-term adhesion against wind suction forces.

Can an edge trim be fixed directly onto thermal insulation on a warm roof?

No. Insulation offers no mechanical resistance against tear-off caused by wind suction at the roof perimeter. The edge trim must be mechanically anchored into a treated timber rafter, a reinforced composite panel, or directly into the structural concrete slab using long expansion anchors passing through the insulation or into a perimeter timber batten.

Texts and standards cited

  • OTConst art. 41measures to be taken at roof edges: appropriate measures to prevent falls from a fall height of more than 2 m (tinsmith scaffold and/or perimeter edge protection depending on the roof slope); on roofs with a slope greater than 60°, work only from scaffolding or a mobile elevating work platform (para. 3).
  • COclient's rights in case of defects in the work: rejection, price reduction, rectification, damages; any clause agreed in advance that restricts or excludes the right to rectification of defects is void if the defect relates to a construction (para. 2bis, since 1 January 2026).