🧱 CFC 214Timber as a load-bearing material: species, grades and moistureChapter 2 of 10 in the section

Strength grading: what the marking on a beam says and what it entails

After reading this chapter, you will know how to decode every stamp on a structural timber beam, check the perfect concordance between the technical specifications of the timber framing drawing and the material delivered, and rigorously apply the mandatory approval procedure with the engineering office should any discrepancy be identified.

Key takeaways

  • Two beams identical in appearance can have completely different strength classes.
  • CE marking according to standard EN 14081 guarantees traceability and the assigned class.
  • Standard SIA 265 governs structural use and design assumptions in Switzerland.
  • Any substitution of class requires the prior written agreement of the structural timber engineer responsible.

Decoding the marking on a structural member and understanding its legal implications

On a timber framing construction site, the visual appearance of a piece of timber in no way allows its load-bearing capacity to be judged. Two planed pieces of spruce, exhibiting similar cross-sections and visible knot densities, can belong to completely divergent strength classes, for instance C18 and C24 for solid timber, or GL24h and GL28c for glued laminated timber. Mechanical strength depends on initial structural grading, carried out at the sawmill by strict visual grading or by machine measurement (bending strength, modulus of elasticity, and density).

Standard SIA 265 sets out the rules for the design and structural verification of timber structures. It requires the use of materials whose mechanical properties correspond exactly to the design values adopted by the engineer.

SIA 265

Each structural timber member or batch must bear marking compliant with standard EN 14081. This physical marking, applied by ink stamp or indelible label on the piece, constitutes the material's identity card. It contains the essential information required to confirm its compliance prior to any installation.

  • The name or logo of the certified manufacturer and the number of the certification body.
  • The product standard applied (for example EN 14081-1 for solid timber or EN 14080 for glued laminated timber).
  • The assigned strength class (e.g. C24, T14, GL24h, GL30h).
  • The moisture content at the time of grading or an indication of seasoning (e.g. KD for Kiln Dried).
  • The traceability code allowing tracking back to the declaration of performance (DoP) certificate.

Ensuring concordance with drawings and managing substitution requests

Upon delivery of timber to the construction site or workshop, the chargehand or site foreman must carry out a systematic check. This involves cross-referencing the class printed on each element (or indicated on the engineering bundle) with the design calculations and working drawings provided by the design office. If the drawing specifies class C24 for joists and the delivered batch bears the C18 marking, the load-bearing capacity of the structure is directly compromised.

It frequently happens in the Romandie market that a specific cross-section or class is not immediately available from the timber merchant. Faced with this procurement constraint, the temptation is great to adapt the piece on the fly, for instance by slightly increasing the cross-section to compensate for a lower grade. This practice is strictly prohibited without explicit validation from the engineering design office.

  1. 1. Goods inwards inspectionCheck the physical marking on the beams received and cross-check it directly against the title block and legend on the framing drawings.
  2. 2. Immediate notificationIn the event of a discrepancy (lower class, missing or illegible stamp), quarantine the piece and issue a non-conformance report.
  3. 3. Modification request to the engineerSubmit a written equivalence request to the timber engineering office before considering any material substitution.
  4. 4. File traceabilityRetain the engineer's written response and record modified elements in the site diary for handover of the works.

Rigorous reading of structural markings in the workshop and on the construction site

Two pieces of timber with identical geometric dimensions can have radically different load-bearing capacities. The difference cannot be seen with the naked eye: it lies in the strength grading. On a framing construction site in French-speaking Switzerland, checking the marking stamped on each timber frame or glulam element is a mandatory inspection step prior to any lifting. Standard SIA 265 establishes the structural design framework for timber structures and requires the use of materials whose mechanical properties are certified and traceable.

Timber strength class
Standardised classification system (for example C24 for solid timber or GL24h for glued laminated timber) defining the permissible stresses in bending, tension, compression, and moduli of elasticity required for structural design in accordance with standard SIA 265.

The ink stamp or label stapled to the piece of timber serves as the material's identity card. It contains precise details that directly engage the liability of the executing contractor during installation.

Constituent elements of standardised marking on structural timber
Marked informationTechnical meaningImpact on the structure
Grading standard / BodyIdentification of the product and third-party certification bodyGuarantee of compliance of machine or visual grading
Strength class (e.g. C24, GL28h)Characteristic stiffness and failure valuesDirectly determines the load resistance calculated by the engineer
Timber moisture content during processing (e.g. M18)Moisture content measured during seasoning or setting outAnticipates shrinkage, creep, and dimensional variation
Timber species (e.g. PCAB for Spruce/Fir)Softwood or hardwood species used for conversionInfluences natural durability and deformation moduli

Concordance with drawings and strict substitution notice protocol

In the field, the chargehand or site foreman must carry out a systematic cross-check between the marking physically present on the delivered timber and the specifications appearing on the cutting list or approved-for-construction erection drawings. If a member marked C18 is delivered instead of the C24 specified on a truss assembly drawing, the piece must under no circumstances be cut or installed.

It frequently happens on the market that supply shortages prompt the substitution of one cross-section or class for another. Even using a higher class (for example installing C30 instead of the planned C24) can involve technical pitfalls, such as a different stiffness modifying the distribution of internal forces in a statically indeterminate joint, or a cost unapproved by site supervision.

  1. Goods inwards inspection on the construction siteInspect the marking on each pack and verify the strength class against the delivery note and framing drawings.
  2. Identification of non-conformanceIf the marking is missing, illegible, or non-compliant with the engineer's drawings, immediately quarantine the member concerned and halt its processing.
  3. Notification under the duty to notifyIn accordance with the Code of Obligations (CO) (art. 365 CO), the contractor shall immediately alert the client or the timber engineer in writing regarding any defect in the material supplied or the need for substitution.
  4. Approval and traceabilityWait for the revised calculation sheet or written confirmation from the engineer before incorporating any replacement member into the load-bearing structure.

By scrupulously applying this marking verification protocol and adhering to the technical validation chain, the site foreman guarantees structural safety, protects their company's liability, and ensures complete traceability of the timber structure in accordance with Swiss recognised rules of the trade.

Management of non-conformances and handling of strength class discrepancies

Two pieces of timber of identical appearance on the construction site may have radically different load-bearing capacities. If the marking printed or stamped on the timber (for example C24 instead of the specified C30) does not match the structural drawings, the member must be set aside immediately. The carpenter can under no circumstances judge the strength of a member visually to approve its installation.

  1. Marking identification and stopping lifting operationsUpon unloading or before installation, check the grading stamp on each load-bearing element. If the marking is illegible or indicates a class lower than required by standard SIA 265 and the drawings, halt the installation of the affected member.
  2. Formal notification under the duty to notifyImmediately inform the client and the structural engineer of the non-conformance identified on the delivered material. In accordance with the contract for work provisions of the Code of Obligations (CO), the carpenter shall report without delay any defect in the material supplied or specified.
  3. Instruction by project management and structural sizingThe timber engineer reassesses the sizing if a substitution is proposed. Only their validated calculation sheet allows acceptance of a cross-section change or an alternative species.
  4. Traceability and disposal of the defective memberMark the non-conforming member indelibly to prevent any accidental installation and record the event in the site diary prior to disposal or replacement.

In the event of a serious failure to adhere to the recognised rules of the trade during the management or execution of a construction project that knowingly endangers life or physical integrity, those responsible face the penalties set out in art. 229 CP. Scrupulous compliance with the technical specifications of standard SIA 265 guarantees user safety and structural durability.

Frequently asked questions

Can a C18 beam be installed if the drawing specifies C24, simply by increasing the section depth?

No. Even if a larger cross-section theoretically compensates for overall strength, slip modulus and deflections differ. The carpenter must never carry out this modification on their own initiative. Any change in class or geometry must strictly be verified and approved in writing by the structural engineer responsible for the project.

What should be done if the strength grading stamp is worn off or illegible on the construction site?

A load-bearing piece of timber without legible marking or a corresponding batch certificate must be deemed non-compliant. Its installation must be stopped, the item set aside, and the certificate of origin and grading requested from the sawmill or supplier. Without documented proof of grading according to standard SIA 265, the piece cannot be incorporated.

What is the site manager's liability in the event of delivery of lower-class timber?

The site manager must exercise their duty to notify in accordance with the provisions of the Code of Obligations (CO) relating to the contract for work. If they discover or suspect a quality defect in the delivered material relative to drawing specifications, they must report it immediately to the client and the engineer to avoid bearing liability for defective execution.

Does glued laminated timber (GL24 or GL28) follow the same marking inspection rules as solid timber?

Yes, glued laminated timber carries a specific marking certifying its mechanical strength class (such as GL24h or GL28c). The site foreman must verify that delivered components correspond exactly to the specifications of the cutting and assembly drawings. No interchanging between homogeneous and combined glulam must be made without prior agreement.

Texts and standards cited

  • norme SIA 265SIA 265: Timber structures - Design and structural verification of timber structures
  • code des obligationsContractor liability regarding materials and duty to notify in the event of defects
  • CP art. 229Breach of the recognised rules of the trade