🧱 CFC 211.1Reinforcement: bending, laps and placementChapter 6 of 10 in the section

Stirrups, links and shear reinforcement: role and spacing

This chapter provides an understanding of the vital mechanical function of stirrups and links against shear force according to standard SIA 262. You will learn how to identify critical support zones, master reading reinforcement drawings and apply the strict procedure prohibiting any moving or removing of transverse reinforcement without formal validation from the civil engineer.

Key takeaways

  • Shear reinforcement prevents brittle and sudden shear failure of reinforced concrete.
  • Closing up stirrup spacing in the support zone absorbs maximum concentrations of diagonal stresses.
  • Moving or removing a link without the approval of the civil engineer directly incurs criminal liability.
  • Execution compliance according to standard SIA 262 guarantees the load-bearing capacity and safety of the structure.

Understanding the mechanical function of stirrups against the risk of brittle failure

On a construction site, transverse reinforcement — stirrups, links and crossties — is sometimes wrongly perceived as simple assembly accessories intended to hold longitudinal main bars. This confusion occasionally leads fixing teams to want to spread or remove a link deemed awkward during the installation of a blockout or during pouring. Mechanically, these steels constitute the shear reinforcement. Without them, a flexural member such as a beam or a thick slab gives no warning before failing: shear failure is instantaneous, brittle and dramatic, unlike flexural failure where cracks on the underside warn users.

Shear force (according to standard SIA 262)
Internal action perpendicular to the longitudinal axis of a structural element, generating diagonal tensile stresses in the concrete web that require the installation of transverse reinforcement to take up the tensile ties.

Concrete resists compressive forces remarkably well, but its tensile strength remains very low. Under the combined effect of bending and shear force, cracks inclined at around 45 degrees develop in the web concrete. Vertical or inclined links literally stitch these potential cracks together. According to the truss model specified by standard SIA 262, the stirrups act as tension steel ties that take up the diagonal force transmitted by the concrete compression struts.

Comparative behaviour of the structure with and without shear stirrups
Mechanical configurationFailure mode observedNature of the failureConsequence for the construction site
Beam without transverse reinforcementDiagonal web shearSudden, without prior deformationImmediate collapse of the span
Beam with stirrups conforming to standard SIA 262Yielding of reinforcement and crushingProgressive with visible deflection and crackingVisual warning and integrity maintained

Managing edge zones, spacing and communication with the engineering consultancy

Shear force is not distributed homogeneously along the length of a load-bearing element. In a simply supported beam carrying a uniformly distributed load, the value of this force is maximum immediately at the faces of the supports and zero at mid-span. This is the exact reason why working drawings show variable spacing. The steel fixer observes a very dense concentration of links in the support and edge zones, sometimes spaced 10 to 15 centimetres apart, whereas the central span zone features much wider spacing, often limited to the regulatory detailing maximum.

  1. Identifying distribution pitches on the scheduleCarefully read the bending schedule and the formwork and reinforcement drawing to identify the first stirrup, which must be positioned less than half a space from the face of the support.
  2. Accurate marking out on main barsMark the exact location of each link with grease chalk, strictly respecting the transition between the closely spaced zone and the standard zone.
  3. Managing a geometric clash or an openingIf an unplanned service duct or sleeve passes through the stirrup cage, do not cut or shift any bar on your own initiative: immediately draft a request for written confirmation.

The contractor applies the design directives without deviating from the drawings provided by the design team. In the event of deliberate non-compliance with the detailing rules on the reinforcement drawings, the criminal liability of the site manager or the foreman is directly engaged pursuant to art. 229 CP, which penalises anyone who intentionally or through negligence breaches the recognised rules of the trade when executing construction work, thereby endangering the life or physical integrity of persons. Removing a stirrup to facilitate the passage of a service duct falls under this provision.

Why transverse reinforcement is concentrated near supports

On a construction site, the temptation to spread or shift stirrups often stems from a practical nuisance: passing service ducts, concentration of longitudinal bars at the junction of a primary beam and a column, or difficulty inserting a vibrator. Considering this density of steel to be excessive demonstrates a misunderstanding of the kinematics of beams and slabs. Shear reinforcement is not used to carry a diffuse load, but to stitch together the diagonal concrete compression struts that form at 45 degrees as soon as the first inclined tensile microcracks appear.

Compression strut
Diagonal volume of compressed concrete that develops between the upper compression chord and the lower tension longitudinal reinforcement, mechanically balanced by the tension of the vertical links or stirrups.

According to standard SIA 262, the acting shear force reaches its maximum value directly at the face of the supports and decreases towards mid-span. Consequently, the pitch between links is never constant over the length of a beam. In the standard zone, wide spacing is sufficient to guarantee the minimum percentage of transverse reinforcement. Conversely, in the support and edge zones, shear dictates tight spacing. Removing every second stirrup to facilitate the passage of a blockout immediately reduces shear load-bearing capacity, without any visible warning signs prior to failure.

Distribution of stirrups and structural functions according to the beam zone
Element zoneLoad levelMain mechanical roleBehaviour if steel is removed
Face of support (length ~ h)Maximum shear force (Vd)Stitching of support struts and anchorage of longitudinal reinforcementSudden shear failure, without prior ductility
Edge zone on wallShear force and torsionTaking up outward thrust and corner bindingSpalling of concrete cover and edge shear
Standard zone (span)Moderate to low shear forceHolding compression bars and skin reinforcementIncreased transverse cracking, risk of buckling of compression bars
Beam-column jointMultidirectional shearConfinement of concrete core under axial compression and bendingCrushing of the joint concrete under seismic or permanent loads

Strict ban on modifying links without the civil engineer's agreement

The reinforcement drawing approved for construction (issued for construction) is a contractual and technical document that commits the structural safety of the building. No general foreman, foreman or steel fixer is authorised to cut, bend back, push aside or remove a link to resolve a geometric clash or facilitate shuttering work. Any clash with inserts, blockout boxes or prestressing ducts must be subject to a written modification request sent to the site management and to the civil engineer responsible for the design.

When a blockout or service duct clashes directly with the link arrangement, the fixing crew must follow a strict protocol to guarantee the durability of the structure while respecting the concreting schedule:

  1. Identification and localised stoppage of fixingIdentify the geometric clash as early as marking out blockouts or placing the first reinforcement cages. Do not cut the vertical legs of existing links.
  2. Transmission of dimensional surveyMeasure precise overall dimensions, dimension the position relative to support gridlines and transmit a sketch or annotated photo to the structural engineer.
  3. Execution of the compensatory solutionImplement solely the compensation scheme specified by the engineer: closer spacing of adjacent stirrups, addition of extra closed links around the opening or provision of certified crossties conforming to standard SIA 262.
  4. Entry in the site diaryRecord the modification adopted, the name of the consultant who validated the variation and archive the detail sketch attached to the concrete pour card.

Managing transverse reinforcement clashes and execution liability

On the construction site, the temptation to spread or cut links almost always arises during geometric clashes: unplanned openings, passing service ducts, congested column heads or complex intersections between primary and secondary beams. These concentrations of steel are not an excess of caution, but meet the requirements of standard SIA 262 to take up compression struts and prevent brittle shear failure.

  1. Identification and local stoppage of reinforcement fixingAs soon as a bundle of stirrups prevents the passage of a blockout, duct or intersecting longitudinal bars, the foreman suspends fixing in the critical zone without cutting any steel.
  2. Formal notice to the site managementThe site manager forwards a request for clarification accompanied by photos and actual dimensions to the civil engineering consultancy, in accordance with the contractor's duty to inform.
  3. Validation of the structural variationThe civil engineer recalculates the shear capacity and proposes a compensatory solution: open links combined with closed crossties, bent-up bars, or controlled relocation with closer adjacent spacing.
  4. Resumption of fixing according to approved drawingThe steel fixers carry out the modification solely on the basis of a working sketch or formal written validation from the engineer, filed in the site diary.

The obligation to comply with reinforcement drawings forms part of the contractor's general performance duties. Art. 364 CO provides that the contractor's liability is governed by the same rules as that of an employee and that he must carry out the work under his personal direction. No transverse reinforcement may be omitted to facilitate concreting without prior technical agreement.

Frequently asked questions

A service duct passes through a beam in the support zone: can we shift the links?

No. In the support zone, shear force reaches its maximum value. Shifting the stirrups creates a gap without transverse reinforcement where the risk of diagonal cracking is highest. Any opening requires the civil engineer's agreement according to standard SIA 262. The engineer will specify the necessary trimming reinforcement, such as closely spaced supplementary links on either side of the blockout or open stirrups tied to closing crossties.

The drawing indicates a 10 cm spacing, but the bars touch the formwork: what should be done?

Links must never be removed to gain clearance. First check the conformity of the link bending against the bar schedule and the correct positioning of spacers. If the actual dimensions prevent simultaneous compliance with cover and geometry, stop fixing. Notify the site management so that the engineer can redefine the transverse steel diameter or authorise a link geometry suited to execution tolerances.

Why are there far more links near columns than in the middle of the beam?

Shear force under distributed load is at its maximum at the supports and decreases towards mid-span. Stirrups and links stitch together the potential cracks inclined at 45 degrees created by diagonal tension. Standard SIA 262 requires this reinforcement to be closely spaced in support and edge zones to take up these intense shear stresses, whereas in the central span, the reduced shear force allows significantly wider spacing between link sets.

Can two closed stirrups be replaced by open links if the reinforcement is too congested?

This substitution is strictly forbidden without clearance from the civil engineer. Closed links with 135-degree hooks provide confinement for the concrete under compression and resist torsion in addition to shear force. Replacing a closed link with an open U-stirrup removes this confinement and risks the reinforcement opening under load. The engineer must calculate and validate any alternative detailing, such as adding certified transverse crossties.

Texts and standards cited

  • norme SIA 262Requirements for the design, calculation and structural detailing of transverse and shear reinforcement in reinforced concrete structures.
  • CP art. 229Breach of the recognised rules of the trade: whoever, when directing or executing construction or demolition work, intentionally breaches the recognised rules of the trade and knowingly endangers the life or physical integrity of persons is liable to a custodial sentence not exceeding five years or a monetary penalty; in the case of negligence, not exceeding three years or a monetary penalty.
  • CO art. 364Obligations of the contractor: liability subject to the same rules as that of an employee; he carries out the work in person or under his personal direction; unless usage or agreement provides otherwise, he procures the necessary resources, equipment and tools at his own expense.