🧱 CFC 273Interior doors: installation, clearances and adjustmentChapter 8 of 10 in the section

Extra-tall doors: warping, stabilised core and number of hinges

Hanging a full-height leaf cannot be improvised with standard tubular panels. This chapter details the flatness requirements set out in the professional rules, the internal composition essential for stabilising a panel above two metres thirty, and the method for distributing the fittings to ensure friction-free closing over time.

Key takeaways

  • Above two metres thirty, an ordinary solid core inevitably sags under its own weight.
  • The SIA 343 standard governs the permissible deviations in warping and curvature of the door leaf.
  • Fitting reinforced edge strips and metal stiffeners neutralises the hygrometric stresses between rooms.
  • A fourth hinge placed below the upper fitting absorbs the most critical pull-out forces.

Understanding the mechanical limits and measuring flatness tolerances

As soon as a leaf exceeds a clear height of two metres thirty, the physics of wood-based materials changes its behaviour. Interior doors of standard dimensions absorb a significant share of internal stresses thanks to their compactness. At extra-tall heights, the lever arm multiplies the warping as soon as the air humidity differs between two adjoining rooms, for example between a temperate corridor and a damp bathroom. If the joiner installs a honeycomb panel or a conventional tubular particleboard core over a floor-to-ceiling height, the leaf bows into an arc or twists within a few weeks of winter use under the effect of underfloor heating.

Permissible deformation by tolerance class of SIA 343
Deformation criterionClass 1 (standard)Class 2 (reinforced)Class 3 (high requirement)
Maximum longitudinal bow8.0 mm over the height4.0 mm over the height2.0 mm over the height
Maximum transverse bow4.0 mm over the width2.0 mm over the width1.5 mm over the width
Permissible twist (free corner)8.0 mm out of plane4.0 mm out of plane2.0 mm out of plane

The commitment made by the interior joinery company to the site management requires vigilance from the tender stage. An order specifying a full-height door without any particular technical specification for the core is a major risk of dispute at acceptance of the works. If the leaf rubs against the strike plate or fails to press against the perimeter seal, the complete rework of the leaf falls to the fitter who failed in the duty to give technical advice.

Specifying a stabilised core and organising the hinge layout

To stabilise an interior door up to three metres, the manufacture of the leaf uses asymmetric or reinforced multilayer composites. The stabilised core combines hard boards, an insulating panel of rigid foam or cork, and two stiffeners integrated into the thickness. These stiffeners take the form of profiled steel tubes or aluminium strips bonded beneath the high-density fibreboard facing. Specialist manufacturers also integrate adjustable metal tie rods accessible from the top or bottom edge, allowing the fitter to correct the warping mechanically with an Allen key once the building is heated.

  1. Checking the squareness of the door frameCheck the strict verticality of the frame jambs with a heavy plumb line and a tubular level. A deviation of one millimetre at the head of the frame considerably amplifies the misalignment on a leaf two metres seventy high.
  2. Positioning the fourth hingeDistribute four hinges instead of the three conventional fittings. Place the first hinge at one hundred and fifty millimetres from the top rail, and the second hinge about two hundred and fifty millimetres below it to take up the pull-out moment.
  3. Mechanical fixing in the openingAnchor the hinge housings with screws at least one hundred millimetres long into the partition reinforcements previously installed by the drywall contractor, in order to prevent any bending of the rebate.
  4. Final three-dimensional adjustmentAdjust the compression of the seal using the micrometric pins. The seal compression must remain even from top to bottom without requiring excessive manual pressure on the lever handle.

Before any installation, store the leaves flat on regular battens spaced sixty centimetres apart in a closed room protected from liquid splashes and draughts. The installation of an extra-tall door must never take place before the screeds and plasters have completed their primary drying cycle, otherwise the flatness of the stabilised panel will be permanently ruined.

On-site installation: stabilising the leaf and adjusting the hinges

As soon as a leaf exceeds the two metres thirty threshold, the climatic conditions on the construction site immediately become critical for the integrity of the work. The delivery of extra-tall elements requires a rigorous protocol: no leaf must be left stored at an angle against a partition or a plasterboard lining, otherwise a permanent bow is induced even before fixing to the frame. Temporary storage is carried out exclusively flat, on a bed of perfectly straight battens spaced no more than sixty centimetres apart, in a room that is necessarily closed, heated and weathertight. Construction site moisture from the recent drying of screeds or fresh plaster is the leading cause of geometric damage to technical interior doors.

To compensate for the residual movement of composite panels and control warping, full-height leaves incorporate mechanical straightening tie rods, machined into the thickness of the core or beneath the edge strips. These axial tension bars, adjustable via a hexagonal socket at the top or bottom of the door, make it possible to apply a prestressing force opposing the measured bow. The joiner adjusts this tension progressively after the leaf is fully installed and subjected to thermal load. This system in no way replaces a rigorous hinge layout: the hinges do not merely carry the dead weight of the leaf, they lock the hung edge against the frame jamb to break the line of mechanical twist of the panel.

Positioning and mechanical role of hinges on extra-tall interior doors
Leaf heightRecommended hingingGeometric layoutMain mechanical force
Up to 2,300 mm3 × 3D hinges2 upper hinges close together (centre distance 200 to 250 mm), 1 lower hinge at 200 mm from the floorTaking up the upper pull-out force induced by the overhang and guiding the lower edge
From 2,301 to 2,600 mm4 × 3D hinges2 hinges at the head (centre distance 200 mm), 1 middle hinge at mid-height, 1 lower hingeNeutralising the longitudinal bow at the centre of the leaf and maintaining the sealing pressure
From 2,601 to 3,000 mm4 to 5 × 3D hinges2 upper hinges, 1 hinge at the upper third, 1 hinge at the lower third, 1 lower hingeReducing the free spans between hinges to prevent cupping and twisting of the stabilised panel

Flatness tolerances according to SIA 343 and contractual commitment

The conformity of an extra-tall door is judged by its flatness in closed service. The check is carried out using a ground aluminium straightedge two metres long and a set of calibrated feeler shims, applied successively along the full height of the jamb, the width at the top rail and the two diagonals of the leaf. A distinction is made between longitudinal bow, transverse bow commonly called cupping, and twist or warp, which corresponds to the angular deviation between the four corners of the joinery. On an element two metres sixty or three metres high, visual assessment is misleading: only the systematic recording of the perimeter gaps and of the flushness against the rebate seal validates the mechanical behaviour of the assembly.

The commitment made by the joinery company when installing non-standard elements is a matter of strict contractual management under the Code of Obligations (CO) and the SIA 118 standard. Installing a full-height leaf in a building whose ambient humidity exceeds the permissible limits, or whose screed has not reached its equilibrium residual moisture, is an unreasonable risk. If the site management requires the closures to be installed before the structural work has fully dried and the final indoor climate has stabilised, the team leader or site manager must give written notice without delay to record the danger of irreversible warping of the wood. Joint acceptance with immediate minutes protects the tradesperson against delayed deformations caused by subsequent seasonal variations.

Handling non-conformities: recording warping and remedial options

When the leaf rubs in the rebate or refuses to engage the strike plate, the intervention follows a rigorous protocol. The joiner first checks the plumb of the frame with a laser level to rule out any movement of the partition. The deflection is then measured on the unhung panel, laid on its edge or held closed, using a 2 m aluminium straightedge and a set of calibrated feeler shims. The values measured at mid-jamb and on the diagonals are compared with the requirement classes of the SIA 343 standard.

  1. Placing under observation in a controlled climateIf the exceedance of the tolerances remains moderate, the leaf is kept under closing pressure for ten to fifteen days after the final heating is commissioned, in order to check whether the stabilised core returns to its neutral equilibrium.
  2. Adjusting the fittings and straightening tie rodsOn leaves fitted with an integrated tie rod concealed in the edge, turning the hexagon nut makes it possible to correct a concave or convex bow of up to four millimetres without damaging the finish of the facings.
  3. Notification of reservations and claim against the manufacturerIn the event of irreversible deformation exceeding the normative thresholds despite correct thermal stabilisation, the site management records the defect in accordance with SIA 118 to demand complete replacement under the factory warranty.

If the designer rejected the option of a core with double aluminium stiffeners despite the joiner's duty to notify recorded in writing, the client bears the loss under the Code of Obligations (CO). Replacement of an out-of-tolerance panel is nevertheless required automatically where the bowing compromises the sound-insulation or fire-resistance functions required by the approvals of the element.

Frequently asked questions

How do you correct a tall leaf that touches the rebate on the lock side at the top?

The correction is made by using the three-dimensional adjustments of the hinges. The upper hinge is moved back towards the splay to give clearance at the head, while the middle hinge is moved forward slightly to counter the bowing of the jamb. If the panel has an internal straightening tie rod, adjust the tension with an Allen key to straighten the edge before considering any rework of the strike plate.

Is a 2500 mm leaf without a metal stiffener acceptable inside a dwelling?

No, this configuration presents a high risk of damage from the very first heating season. Without aluminium strips or integrated stabilising bars, the temperature difference between the corridor and the room creates an asymmetric thrust that a simple tubular panel cannot withstand. The manufacturer withdraws its warranty from two metres thirty in height without certified structural reinforcement.

What out-of-plumb tolerance applies to a tall entrance door according to SIA 343?

The SIA 343 standard sets the permissible general flatness deformation according to the tolerance class agreed in the contract. For an extra-tall door of class 2, the maximum deflection tolerated under the 2 m straightedge is generally 4 mm. Beyond this value, measured under stabilised climatic conditions, the leaf is judged non-conforming and must be straightened or replaced.

Why place two hinges close together at the top rather than an even spacing?

Over a height exceeding two metres thirty, the lever arm exerted by the mass of the panel applies a major horizontal pull-out stress on the upper anchorage. Placing a second hinge at 250 or 300 mm below the head hinge makes it possible to take up this pull-out moment in the frame, while the lower hinge carries the vertical load without risk of mechanical shearing.

Texts and standards cited

  • SIA 343Doors: requirements, classification and dimensional and flatness tolerances
  • SIA 118General conditions for the execution of construction works and handling of defects
  • Code des obligationsGeneral rules of the contract for work and services and liability for defects in the work