🧱 CFC 212Mobile, suspended and temporary structuresChapter 3 of 10 in the section

Cantilever scaffolding: transferring load to the existing structure

When the ground at the base of the facade is obstructed or impassable, cantilever scaffolding rests directly on the existing structure. This chapter details the verification of the bearing capacity of supporting slabs, the dimensioning of metal brackets, the rules for penetrating insulation and the drafting of the justification required by regulations to guarantee the safety of the structure.

Key takeaways

  • Verify the slab's capacity to absorb point loads transmitted by the supporting brackets.
  • Art. 29 OTConst requires a written measure with a specialist in the event of any deviation from standard protective measures.
  • Penetrate the insulation build-up while guaranteeing waterproofing and the absence of critical thermal bridges.
  • Check the tensile and shear strength of the anchors using on-site pull-out tests.

Transferring loads to the slab and verifying the existing structure

Erecting cantilever scaffolding requires a rigorous analysis of the reinforced concrete substrate. Unlike a base-supported structure hinged on the ground, a suspended or cantilevered structure transfers all vertical loads and overturning moments to the edge of the slab or the upper floor. Before any erection work, the site manager must ensure that the existing slab can support the support reactions generated by the self-weight of the scaffolding, live loads and wind pressure.

The structural engineering specialist calculates the forces transmitted to the fixing points. Compressive forces at the lower arm of the bracket can reach several tens of kilonewtons. The absence of sensitive reinforcement or prestressing ducts at drilling locations must be verified. If the slab is recent, the compressive strength of the concrete must be confirmed before loading the temporary structure.

Cantilever bracket
Triangulated metal structure fixed to the facade or the edge of a slab, intended to support the standards and decks of scaffolding when no direct ground support can be achieved.
  1. Analysis of formwork and reinforcement drawingsIdentify slab thickness, rebar diameter and concrete cover to position anchors without damaging the main reinforcement.
  2. Calculation of support reactionsDetermine the dead and live loads applied to each bracket, taking into account the required scaffolding class.
  3. Validation of mechanical strengthObtain written confirmation from the civil engineer certifying that the concrete and the slab can withstand punching shear and shear forces.

Facade penetrations, waterproofing and anchor installation

Penetrating the building envelope represents a critical point when installing cantilever brackets. When the facade includes external thermal insulation or rainscreen cladding, extension tubes or mounting brackets must pass through these layers without crushing the insulating material. The use of rigid metal spacer sleeves allows the load to be transferred directly to the structural concrete.

Constraints and solutions for bracket facade penetrations
Type of facadeTechnical riskRequired assembly arrangement
Exposed reinforced concreteSurface punching and spallingSteel spreader plate with neoprene backing
External wall insulation (ETICS/EWI)Crushing of insulation under loadTubular steel spacers anchored into concrete
Rainscreen facade (cladding)Damage to sub-structuresLocalised removal of panels and direct anchoring

Water tightness and airtightness around the anchor penetration must be treated with care to avoid any moisture ingress into the building physics. Fitting flexible waterproofing collars or polymer sealing gaskets around anchor rods or through-tubes is essential. The 2026 revision of the Construction Work Safety Ordinance reiterates the priority given to the overall stability of assemblies.

The lead erector records in the scaffolding acceptance certificate the type of mechanical or resin anchors installed, the embedment depth and the applied tightening torque. In addition to best trade practice for assembly, the safety plan drawn up in accordance with art. 4 OTConst contains details of regular inspections of the condition of anchors and brackets throughout the construction site duration.

Written formalisation of equivalent protections and specialist measure

When the installation of ground-supported standard facade scaffolding is impossible and conventional solutions do not apply, cantilever assembly requires rigorous engineering measures. In accordance with art. 29 OTConst, when it is impossible to erect standard facade scaffolding or perimeter edge protection, the contractor must define equivalent protective measures, set down in writing with the assistance of an occupational safety specialist.

The scaffolding erector cannot rely on visual estimates regarding load transfer. Heavy-duty brackets or truss girders transmit concentrated compressive and tensile forces that must be verified for each support point. The appointed specialist assesses the interaction between the temporary works and the existing concrete, taking into account dead loads, live loads and wind actions.

Anchor checks and waterproofing of facade penetrations

Erecting suspended or cantilever scaffolding requires clean penetration of the insulation and waterproofing system. The team leader applies a strict anchoring protocol to prevent any water ingress into the external insulation envelope and to guarantee the mechanical strength of fixings.

  1. Drilling and cleaning the substrateDrill into the load-bearing material using a suitable drill bit. Clean the borehole using compressed air and a wire brush to remove any concrete dust that could impair adhesion.
  2. Installing the anchor rod and anchoringInsert the mechanical expansion anchor or threaded rod with chemical resin according to the manufacturer's specifications. Apply the required tightening torque using a torque wrench.
  3. Penetrating insulation and waterproofingFit a flexible sealing sleeve or an EPDM collar around the penetration. Inject a waterproof sealant compatible with the external insulation to prevent any thermal bridge and moisture ingress.
  4. On-site tensile testCarry out pull-out tests using a pull tester on a sample of anchors to validate the actual strength of the concrete substrate.
Anchor inspection matrix for cantilever structures
Component inspectedValidation criterionTolerance / Requirement
Strength of concrete substrateOn-site pull-out test using pull testerComplies with structural calculation values
Anchor tightening torqueCheck using torque wrenchExact value specified by manufacturer
Insulation penetrationCable gland or EPDM sleeve installedAbsence of voids, guaranteed water tightness
Visual check of the supporting slabAbsence of cracks or spallingCheck before and during loading

In the event of non-performance of a contractual obligation during fixing or assembly works, contractor liability is governed by CO. Furthermore, regarding construction site safety, OTConst requires the employer to appoint a competent person responsible for safety, capable of giving the required instructions to the erection teams.

Managing structural anomalies and anchor failures on the construction site

Installing cantilever scaffolding exposes the erection team to major structural unforeseen circumstances on existing buildings. When the concrete quality proves lower than specified, or if drilling encounters unlocated rebar, the integrity of the load transfer is immediately compromised. Discovering non-through cracks, degraded concrete or mislocated penetrations requires the immediate cessation of bracket extensions and the closure of access to the relevant platform.

  1. Immediate securing of the zoneClose access to the relevant scaffolding levels and set up physical barriers on the ground beneath the footprint of the suspended structure. Lock out hoists and winches.
  2. Formal notice to the clientIn accordance with CO, the contractor shall immediately inform the client when the structure provided or the designated substrate exhibits defects likely to compromise the timely or safe execution of the works.
  3. Technical assessment and corrective measuresCall in the civil engineer to perform a strength check by means of a pull-out test on adjacent anchors. Under art. 29 OTConst, any necessary alternative protective measures must be set down in writing with the assistance of a specialist.
  4. Return to service and waterproofing checkAfter reinforcing the fixing and repairing the facade penetration, carry out a joint acceptance inspection before re-authorising access to the other trades.
Corrective actions in the event of observed damage to the substrate or anchor
Identified anomalyImpact on the structureImmediate action to apply
Slippage or play in a mechanical anchorLoss of preload and uneven redistribution of loadsHalt erection, unload the bracket and install an emergency through-bolt fixing
Water infiltration at the facade penetrationDegradation of insulation and risk of internal corrosionRemove collar, dry out and fit a flexible waterproofing sleeve with a waterproofing specialist
Micro-cracking around slab bearing zonesStress concentration point detrimental to the concreteSuspend use and request a structural engineering assessment

Frequently asked questions

What should be done if the concrete strength is insufficient for the anchors?

Expansion or mechanical anchoring must be stopped immediately and the site engineer informed. In the case of low-strength or hollow-core concrete, the solution often involves using through-rods secured against backplates on the rear of the slab, or using specific chemical anchors validated by an additional calculation note from the specialist.

Who must validate the load-bearing capacity of an existing slab before mounting brackets?

Verifying the load-bearing capacity is the responsibility of the client and their civil engineers. The scaffolding erector must obtain written proof of this structural validation, including the allowable loads per square metre and the support reactions at the fixing points, before starting to erect equipment on the construction site.

How can an insulated facade be penetrated without creating a thermal bridge or moisture ingress?

The penetration must use rigid spacer sleeves that pass through the insulation without compressing it. Water tightness and airtightness are provided by sealing sleeves bonded to the breather membrane or vapour barrier before tightening the bracket. Connection details must be coordinated with the facade contractor.

What must be done if unexpected work requires the removal of a restraint anchor?

No anchor may be removed without first installing a substitute anchor in the immediate vicinity, sized to take equivalent loads. This operation requires the agreement of the scaffolding foreman and must be recorded on the inspection report in order to maintain the compliance of the structure.

Texts and standards cited

  • OTConst art. art. 29 OTConstother fall protection: when it is technically impossible or too dangerous to erect perimeter edge protection, facade scaffolding or a safety net, equivalent protective measures must be taken and set down in writing with the assistance of an occupational safety specialist.
  • CO art. COmaterials and site: the contractor is liable for the good quality of materials supplied; if materials supplied by the client or the site designated by the client are found to be defective, or if any other circumstance compromises the regular or timely execution of the work, the contractor shall immediately inform the client, failing which the contractor shall bear the consequences (para. 3).