🧱 CFC 250Cold water, hot water and recirculation distributionChapter 5 of 10 in the section

Crimp it right: calibrated tool, jaw, visual check and unpressed fitting

This chapter details the rigorous method for guaranteeing absolute tightness of multilayer fittings. You will know how to match jaw and fitting without error, check the calibration status of your electro-hydraulic crimping tools, validate each socket engagement by direct visual inspection and formalise a systematic checklist before any service duct is closed or any screed is poured.

Key takeaways

  • A mismatch between the jaw profile and the fitting brand causes delayed leaks.
  • The detachable indicator ring and the insertion window guarantee full engagement before crimping.
  • A crimping tool not calibrated according to the manufacturer's guidelines loses the nominal compression force required.
  • A signed visual check, fitting by fitting, remains the only guarantee before the ducts are finally sealed.

Strict compatibility between crimp profile, fitting and machine maintenance

In plumbing installations according to the SVGW guidelines for drinking water distribution, the use of multilayer pipes requires complete geometric compatibility between the pipe, the fitting sleeve and the crimping jaw. The building sector all too often encounters major damage caused by the assumed interchangeability of tooling. Each manufacturer approves a specific impression profile (such as the TH, U, H or B profiles). Fitting an unsuitable jaw on a crimping tool produces incomplete or asymmetrical deformation of the stainless steel ring. Even if the network sometimes withstands the initial pressurisation, temperature variations and water hammer eventually push the fitting apart under the screed or in an inaccessible service duct.

Inspection matrix for electro-hydraulic crimping tools
ComponentCheck point on siteRisk in case of non-conformity
Press jawEngraved profile matching the fitting manufacturerAsymmetrical crushing, cutting of the EPDM O-ring
Crimping tool rollersNo axial play, cleanliness and regular greasingLinear loss of force, incomplete press cycle
Calibration plateValidity of the annual inspection according to the service due dateInsufficient hydraulic pressure without electronic warning
Fitting sleeveInternal cleanliness, continuous presence of the O-ringsSlow leak through pinching or tearing of the seal

Preventive maintenance of electro-hydraulic crimping tools is the second indispensable technical safeguard. A machine that has accumulated several thousand cycles suffers wear of its hydraulic pump and ageing of its relief valves. Manufacturers' recommendations require periodic annual calibration, shown by a dated sticker on the tool housing. The installer checks this date before each phase of water distribution. A tool unable to reach its nominal compression force (generally 19 to 32 kN depending on the diameter) forms a ring that looks regular but lacks the mechanical strength needed to anchor the grooves in the aluminium layer of the multilayer pipe.

The checklist protocol and individual visual inspection before closure

Repairing a leak in a closed service duct or under a solid timber floor generates costs out of all proportion to the time needed for inspection. Art. 364 CO subjects the contractor's liability to the same rules as that of the employee, obliging them to carry out the work with care, in person or under their personal direction. On multi-family housing or administrative building sites, the plumbing foreman personally takes responsibility for validating the concealed connections. This task cannot be delegated to an outside party: it is built around an individual visual check before the plasterboard fitter fixes a single plasterboard sheet or the screed layer starts pouring.

  1. Calibrating and deburring the pipeCut the multilayer pipe at a right angle using a suitable pipe cutter, then calibrate and deburr the inside and outside at the same time to remove any swarf and restore the circular cross-section.
  2. Checking the insertion depthPush the fitting in until it reaches the mechanical stop, visually checking for the white pipe through the transparent or slotted inspection windows of the crimping sleeve.
  3. Carrying out the complete crimpPosition the jaw perpendicular to the pipe axis, seating it against the guide collar, then hold the trigger until the automatic release signals the end of the cycle.
  4. Physical marking and releaseRemove the plastic indicator ring or draw an indelible marker line on the crimped metal, then tick off the connection on the distribution diagram in the site file.

This systematic protocol eliminates the human error inherent in fast-paced construction sites. During unplanned interruptions — end of the day, lunch break, restocking of parts — a pipe pushed in by hand but left uncrimped can easily be mistaken for a fitting that has been definitively crimped. The absence of an indelible marker line or the persistence of an indicator collar alerts the installer on the inspection round. Combined with the hydrostatic pressure test prescribed by the SVGW guidelines, this rigour of execution eliminates the risk of insidious flooding that often only shows up several weeks after residents move in.

Mechanical leak function and tightness tests according to the SVGW guidelines

The modern multilayer fitting incorporates an O-ring profile designed to cause a deliberate leak as long as the mechanical crushing of the ring has not been carried out. This leak-before-crimp function is a major technical safeguard, but it never replaces the installer's rigour on the layout. In a service duct or suspended ceiling, an engagement without crimping can hold by simple friction during water filling without dynamic pressure, masking the error for several days. From the first draw-offs in operating conditions, water hammer and thermal expansion eventually push the pipe out of the fitting body, releasing the flow at a pressure of four to six bar behind a finished partition.

  1. Preliminary low-pressure air testInflate the isolated network to 150 hPa using a compressor fitted with an oil separator. Allow the temperature to stabilise for ten minutes. Hold the test pressure for at least a further ten minutes. Any pressure gauge drop indicates a fitting left open or an uncrushed plastic guide ring.
  2. Pneumatic mechanical strength testFor distribution sections with an outside diameter of 50 mm or less, gradually raise the air pressure to 3 bar on the precision pressure gauge. This test confirms the axial hold of the crimped rings under thrust before any hydraulic filling.
  3. Filling with drinking water and complete purgingFill the installation with filtered drinking water, methodically purging the air from the highest point. Apply the hydraulic test pressure equal to the maximum service pressure increased according to the manufacturer's requirements and the SVGW guidelines, observing the pressure plateau on a calibrated dial pressure gauge.

Duct locking, individual checklist and handover to finishing work

Damage caused by an uncrimped fitting stems from a break in the internal quality assurance chain. On multi-family housing or administrative building sites, the closing pace imposed by the plasterboard fitters and screed layers creates a critical friction zone. No plumber may authorise the closure of a service duct, the fitting of an access hatch or the pouring of a screed without having personally carried out a tactile and visual check on every connection point. The physical check guarantees absolute correspondence between the geometry of the jaw used and the impression left on the stainless steel sleeve.

Physical and documentary inspection protocol before duct closure
Check pointSwiss conformity criterionConsequence in case of non-conformity
Viewing windowMultilayer pipe pushed in to the stop, visible in the openings of the plastic ring.Risk of pull-out under pressure; complete removal of the part and square cut required.
Crimp impressionContinuous bead without asymmetrical deformation, matching the die profile specified by the manufacturer.Ovalisation of the pipe, partial crushing of the O-ring; immediate replacement of the fitting.
Detachable plastic indicatorFusible ring or indicator clip broken and removed after the calibrated jaw has completed its pass.Suspicion of a fitting merely pushed in dry; pneumatic test or crimping to be redone.
Indelible marker lineTransverse line drawn on the metal body and the pipe immediately after the crimp has actually been made.Checklist cannot be validated; destructive inspection or individual re-examination required.
Sleeve and expansionThermal insulation and fire-stop sleeve fitted without mechanical tension on the crimped branches.Structure-borne sound transmission and shear stress at the shoulders.

The checklist is not a mere office formality, but the material proof of self-inspection required by standard SIA 118 when the works are handed over. Each riser, each floor take-off and each concealed branch is marked on the installation drawing. The foreman records the crimping date, the serial number of the electro-hydraulic crimping tool, the date of its last calibration at an approved centre and the operator's signature. This document is countersigned by the plumbing site manager before being passed to site management as the formal release of the hold point.

Crisis management: leaking fitting, closed duct and water damage

Discovering a leak on a multilayer fitting after filling is an absolute construction site emergency. If a pressure drop or the appearance of damp reveals an uncrimped or poorly pressed fitting in a service duct that has already been lined, the response must be methodical. The first measure is to shut off the riser base valve and drain the affected part of the installation to immediately stop the soaking of neighbouring materials.

  1. Non-destructive location and surgical openingLocate the emergence point with a thermal camera or a contact moisture meter before any demolition. Open the plasterboard lining cleanly alongside the riser, without destroying the hangers or cutting other adjacent pipes.
  2. Fitting diagnosis and mechanical removalIdentify the precise cause: sleeve not crimped, wrong jaw profile, missing bevelling that sheared the O-ring, or incomplete engagement visible at the inspection windows. Never attempt to re-tighten a defective multilayer fitting: the stainless steel or aluminium ring must be cut off and the part replaced entirely.
  3. Replacement and reinstatement of the sectionCut the multilayer pipe square behind the deformed area. Calibrate and deburr the end of the new pipe, insert the sliding coupling or the repair sleeve approved by the system manufacturer, then crimp with the jaw of the prescribed profile.
  4. Repeating the tests and joint inspection recordRepeat the pressure test according to SVGW guideline W3, first with dry air or inert gas if the works are still exposed to frost, then with water. Record the report signed by the plumbing foreman and site management before closing the service duct again.

When water has run under a floating screed or soaked mineral insulation, coordination with the site manager is essential to carry out technical drying with absorption dehumidifiers. The individual checklist and the photos of each hydraulic connection are then the only supporting documents attesting to the installer's good practice towards the insurers.

Frequently asked questions

How should you react if a plasterer has closed a duct before the checklist protocol was validated?

You must refuse acceptance of the lining with site management and demand the reopening of temporary hatches if no joint inspection or photographic record has been logged. The pressurisation according to the SVGW guidelines must absolutely be witnessed in person on all branches. Without this prior physical check, the risk of a concealed leak places total responsibility on the plumber.

Can a TH profile jaw be used on a multilayer fitting designed for a U profile?

No. Mixing crimp profiles is strictly prohibited, even if the fitting appears mechanically held after the ring has been crushed. Jaw impressions apply specific geometric stresses intended to compress the O-rings without destroying the metal core of the pipe. Using a non-approved geometry immediately voids the SVGW approval of the distribution system manufacturer and compromises tightness under thermal cycles.

Why does the mechanical leak function of an uncrimped fitting not always drip at low pressure?

Some controlled-leak fittings self-seal through simple friction of the elastomer or through dry friction when the water pressure rises too abruptly. The initial low-pressure compressed air test recommended by the SVGW guidelines reliably reveals these crimping omissions thanks to the differential pressure gauge, whereas hasty water filling would falsely press the seal against the wall without definitive crimping.

Which document protects the plumber in case of water damage occurring after the floors have been laid?

The detailed pressure test report countersigned by site management, together with the individual checklist of each crimped fitting. This file proves that the pressure holding stages and the visual inspection of the sleeves were carried out in accordance with the rules of the trade. Without this self-inspection protocol, the plumbing company is presumed liable for the non-conformity of the hydraulic assembly in the duct.

Texts and standards cited

  • Directives SSIGE W3Guidelines for drinking water installations, execution principles and pressure tests
  • Norme SIA 118General conditions for the execution of construction work, acceptance of works and handling of defects