🧱 CFC 250Drinking water: introduction, protection and meterChapter 9 of 10 in the section

Taking over the old: lead, corroded galvanised steel and what we refuse to extend

Faced with ageing galvanised steel or lead pipework, the sanitary installer cannot settle for a quick connection. You will learn how to assess the real condition of existing pipes, identify the risks of scaling and galvanic perforation, and draw up a written record that can be relied upon before starting your connection work.

Key takeaways

  • Lead pipes must be systematically replaced up to the distributor in accordance with SSIGE guidelines.
  • Scaled galvanised steel drastically reduces flow and conceals perforating corrosion under the sleeves.
  • Connecting copper upstream of a galvanised pipe causes rapid electrochemical destruction through a galvanic cell effect.
  • The written record of the existing condition protects the installer before any modification to an ageing network.

Diagnosing galvanised steel and lead before any takeover quote

During an interior renovation, connecting a new manifold or modern fixtures to an existing installation begins with a physical diagnosis of the materials in place. The presence of lead in the internal drinking water distribution network is a major sanitary non-conformity. According to the SSIGE guidelines, lead is prohibited for conveying water intended for human consumption because of the risk of heavy metals dissolving. The technical rule is unambiguous: any lead section found downstream of the service entry must be removed and replaced as far as the manifold or the main shut-off valve.

For galvanised steel pipes, an external visual check almost never reflects the remaining useful cross-section. With age and the hardness of the water supplied, these pipes become scaled and develop tuberculated rust deposits that reduce the internal diameter by half, or even three quarters. A one-inch threaded pipe (DN 25) can have a free passage equivalent to a DN 10. Connecting a new high-flow distribution to a choked riser causes dynamic pressure drops as soon as a second draw-off point is opened.

Wear indicators of old metals in internal distribution
Material foundVisible or measurable symptomHydraulic or sanitary consequenceAction required on the construction site
LeadMatt grey metal, malleable, swollen wiped jointsToxic migration of lead into stagnant drinking waterAbsolute refusal to extend, full replacement required
Galvanised steelOxidised threads, white weeping under insulationChoked flow, rusty water after prolonged shutdownProbing by removing an air vent, checking the remaining wall thickness
Galvanised steelFrequent water hammer, whistling noises at draw-offStructural weakening of threads through crevice corrosionMeasuring dynamic residual pressure with a floor-level flow meter

Setting the limits of the work and notifying the client of the existing condition

As soon as an installer puts a wrench on a rusted threaded fitting to screw on a transition to multilayer or stainless steel, they take on operational responsibility. The mere torsional force applied to an old galvanised steel pipe can break the next thread, which is embedded in an inaccessible service duct. If the tradesperson makes this connection without formal warning, the customer will blame them for the overall drop in flow, the sudden temperature variations in the shower and later leaks on the parts that were not renovated.

Under art. 365 CO, the contractor informs the client when a circumstance jeopardises the proper execution of the work. When faced with degraded old pipework, the duty to notify is exercised before the final quote is drawn up or immediately after hidden networks are discovered during demolition. The installer must record the state of deterioration of the upstream network and state in black and white the physical limits of their connection.

  1. Joint inspection record of the existing installationPhotograph the planned connection points, note the traces of external oxidation, and measure the static pressure and the dynamic pressure at the existing taps before any water shut-off.
  2. Defining the boundary of the workMark the exact separation point between the retained installation and the new network by fitting an isolation valve with a non-return valve or an insulating fitting, depending on the configuration.
  3. Written notification to the clientDraft a notice pointing out the risk of mechanical failure during dismantling, the persistence of upstream pressure losses and the refusal to guarantee the nominal flow if the riser remains in galvanised steel.
  4. Option of a variant or refusal to carry out the workOffer in the quote the complete replacement as far as the basement manifold, or record a release of liability signed by the customer if they refuse the overall refurbishment.

Connecting to mixed risers and preventing galvanic corrosion

Connecting a modern multilayer or stainless steel distribution to a retained riser requires strict compliance with the SSIGE guidelines on drinking water installations. The main risk lies in the formation of galvanic couples and the impairment of water quality. According to the SSIGE W3 guidelines, the flow-direction rule strictly prohibits placing a more noble material, such as copper or certain brass alloys, upstream of galvanised steel pipes. The copper ions released by the water flowing through a new section would cause, on contact with the zinc and steel downstream, perforating pitting corrosion under metallic deposits.

Beyond the metallurgy, mechanical connection to old threaded steel pipe exposes the refurbished network to major hydraulic faults. The action of the jaws of an angle wrench or the vibrations transmitted by a reciprocating saw loosen the calcium carbonate encrustations and rust pustules lining the inside of the riser. Without a complete purge and a hydrodynamic flush of the retained part beforehand, this debris migrates instantly to the new equipment as soon as the system is pressurised, clogging thermostatic heads, pressure-regulating filters and non-return valves.

Admissibility of pipe transitions according to the nature of the retained upstream network
Upstream pipe materialPlanned downstream materialTechnical admissibilityMandatory interface measure
Corroded galvanised steelCopper / Copper alloyAdmissible only downstream of the galvanised steelFitting a dielectric insulating fitting and a bronze or malleable cast iron adapter sleeve
Copper / Copper alloyGalvanised steelProhibited by the flow ruleComplete replacement of the downstream steel section with pipework insensitive to copper ions
Scaled galvanised steelCross-linked polyethylene / MultilayerAdmissible without restriction on directionMechanical fitting with external clamping or brass threaded transition without axial mechanical stress
LeadAny new materialProhibited for drinking water distributionTotal replacement of the upstream pipe as far as the meter or main distributor

Joint inspection record, limits of work and formal notice to the client

The sanitary installer cannot guarantee the performance of a new terminal distribution if the upstream network has a useful bore greatly reduced by encrustation. Connecting a modern manifold without stating reservations makes the company liable for the final flow in use. Art. 365 CO provides that if the material supplied by the client or the ground designated by them is found to be defective, or if another circumstance jeopardises the proper or timely execution of the work, the contractor must inform the client. The notice must be drawn up in writing before any quote is signed or any addendum is approved.

  1. Pressure and flow measurementRecord the static pressure and the dynamic pressure at the planned cut-off point using a calibrated test sleeve fitted with a pressure gauge and a discharge valve.
  2. Endoscopic inspection of the penetrationInsert an inspection camera one linear metre into the retained pipe to record in photographs the thickness of limescale deposits and the residual ovalisation.
  3. Drawing up the joint inspection recordDraft the record on site with the representative of site management or the client, stating the actual measured internal diameter against the theoretical nominal diameter.
  4. Notification of reservations and limits of workState in the quote that the warranty on the work stops strictly at the mechanical junction point and that no terminal flow in use can be guaranteed.

Where the client refuses to replace ageing pipes despite the technical notification, art. 369 CO provides for the exclusion of the client's rights in respect of defects in the work where the defective execution is personally attributable to them, notably through instructions given contrary to the contractor's formal notices. In practice, the sanitary tradesperson refuses to carry out the connection if the lead pipework supplies a point of human consumption or if the remaining thickness of the galvanised steel no longer allows a watertight thread complying with the recognised rules of the trade to be made.

Handling failures, rupture on a corroded network and stopping work

When a connection to an existing network causes an unforeseen rupture — a galvanised steel thread sheared flush with a sleeve by torsion, a tapping perforated by corrosion under the limescale deposit, or the chance discovery of a lead section hidden under an insulation shell — the sanitary installer stops the work. Continuing to tighten or attempting a makeshift brazing on weakened metal makes the company liable for all the resulting water damage. The SSIGE guidelines require the wholesomeness of drinking water and a draw-off flow suited to each fixture to be preserved, two requirements that cannot be met on pipework whose passage section is blocked by rust encrustation.

  1. Isolating and draining the sectionClose the shut-off valve located upstream, lock out the riser, drain the residual water through the low drain and fit a watertight mechanical plug to rule out any risk of flooding if third parties operate the valve.
  2. Joint inspection record of the damageRecord the physical condition of the pipework with the client or the representative of site management: photograph the cross-section of the pipe, measure the loss of metal thickness and record in writing the degree of internal scaling.
  3. Notification under the duty to notifyDraft a written notice stating that the ageing condition of the existing network jeopardises the durability of the work, rules out any guarantee of watertightness and makes complete replacement necessary, in accordance with the obligations of the Code of Obligations (CO).

Until the client has approved an addendum providing for replacement of the corroded section as far as the distributor or the main meter, the work remains suspended. If the customer demands that the connection to the degraded pipework be maintained in order to reduce refurbishment costs, the installer states in writing their refusal to take responsibility for future defects or withdraws from the work so as not to breach the technical rules of the SSIGE guidelines and of standard SIA 118 on the conformity of water installations.

Frequently asked questions

Can a multilayer pipe be connected directly to an old galvanised steel thread?

Direct connection is technically possible using a brass or bronze screw fitting, but it remains inadvisable without a prior check of the condition of the existing thread. If the crests of the threads are thinned by corrosion or if the inside of the pipe shows a section reduction of more than one third of the nominal diameter, tightening risks splitting the steel. The installer must first brush the thread and check the remaining thickness.

What to do on discovering a lead internal distribution pipe?

The presence of lead pipes in the internal drinking water distribution contravenes the sanitary requirements of the SSIGE guidelines on drinking water quality. Any tapping or extension on this toxic metal must be refused. The installer warns the client by a written record and quotes the complete replacement of the pipe as far as the meter, using certified stainless steel or synthetic pipes.

How to respond to a client who refuses to replace a scaled steel riser?

The sanitary installer must give notice under the duty to notify by registered letter, describing the severe scaling and the measured pressure loss. The document states that connecting new fixtures to this riser cannot guarantee the minimum flow or prevent flow noise. The company expressly states reservations declining any guarantee on water pressure and on the later appearance of leaks through perforating corrosion on the retained network.

Which transition fittings should be chosen to limit galvanic corrosion on iron pipe?

To connect a modern copper or synthetic pipe to a retained galvanised steel pipe, a spacer piece in bronze or in dezincification-resistant brass must be inserted. According to the SSIGE guidelines, galvanised steel must always be upstream of copper in the direction of fluid flow to prevent the transport of cupric ions. The installer can also fit a dielectric insulating fitting to neutralise the galvanic cell.

Texts and standards cited

  • norme SIA 118General conditions for the execution of construction work
  • directives SSIGEGuidelines for drinking water distribution in buildings
  • code des obligationsGeneral rules of the contract for work and the contractor's duty to notify