Key takeaways
- Residual-current protection and the earth loop are the first line of defence against electric shock.
- The hierarchy of risks requires dangerous circuits to be neutralised before cosmetic refurbishment.
- The written staged plan sets out to the client the strict limits of each intervention.
- The partial safety report certifies only the compliance of the circuits made safe during the completed stage.
Ranking technical emergencies: residual-current protection and earthing before surface refurbishment
On an old installation that is undersized or deteriorated, the complete replacement of the embedded wiring is a cost that the client cannot always bear in one go. The electrician must distinguish the immediate life-threatening risk from a mere comfort defect or cosmetic ageing. The absolute priority is protection against electric shock by direct or indirect contact, as well as the risk of fire caused by overcurrents or overheating on conductors whose breaking capacity has been exceeded.
- Level 1: Immediate fatal danger. Total absence of earth connection on accessible sockets, bare textile-insulated conductors, voltage present on metal enclosures or neutral fuses cut.
- Level 2: Active protection of persons. Absence of a residual-current device (RCD) rated at 30 mA on the final circuits of damp rooms or general-purpose sockets.
- Level 3: Protection of property and cables. Thermal overload of lead-sheathed or metal-conduit wiring caused by overcurrent protective devices with ratings unsuited to the copper cross-sections.
- Level 4: Functional improvement. Replacement of obsolete accessories posing no direct mechanical danger, increasing the number of sockets per room or separating the lighting circuits.
The first physical measure is to make the safety infrastructure at the distribution board sound: establish or check the earth loop, verify the earth resistance value, connect the main equipotential bonding to the water mains and metal structures, then install a main residual-current circuit breaker or dedicated 30 mA residual-current switches for the priority groups of circuits. This preventive action provides immediate automatic disconnection in the event of an insulation fault on the old wiring temporarily kept energised.
Formalising the phasing and limiting the validity of the interim safety report
A piecemeal compliance upgrade cannot rely on a mere verbal agreement. The installation electrician draws up a written staged plan that rigorously documents the initial state of the premises, the circuits accepted and modified during the current stage, and the scope of the old installations that remain under the owner's operating responsibility. This contractual document specifies the agreed chronology, the geographical limits of each phase and the maximum deadlines for carrying out the following stages.
| Stage | Technical scope | Required checks | Documentary deliverable |
|---|---|---|---|
| Stage 1: Emergency | New board, earthing, fitting of 30 mA RCDs, making safe the kitchen and wet rooms | Continuity of the protective conductor, RCD tripping, insulation of the circuits made safe | Stage measurement record and partial safety report |
| Stage 2: Bedrooms and corridors | Replacement of insulated conductors in steel conduit, fitting of sockets with protective contact | Fault loop impedance, disconnection time, insulation test | Supplementary stage safety report |
| Stage 3: Outbuildings | Circuits for cellars, attics, outdoor sockets and supply to annexes | General continuity test, outdoor RCD tripping, visual inspection | Final safety report for the entire supply point |
From a regulatory standpoint, the operator remains responsible for the condition of the installation. When a stage is completed, the installer holding the installation permit carries out the final inspection of the works carried out or modified only. They record the results in the measurement record and draw up a partial safety report clearly stating the circuits verified and an explicit list of the parts of the installation not dealt with.
This partial document does not release the operator from their overall obligations towards the network operator or the inspection body. If the client keeps clearly defective sections in service without commissioning the next stage, the contractor formally notifies them of these defects, in accordance with the obligations of art. 365 CO governing the information owed by the tradesperson. The electrician keeps a copy of the written warnings, the updated single-line diagrams and the insulation measurements for each phase delivered.
Isolating obsolete circuits and managing transitional circuits
When the budget forces the initial intervention to be limited to replacing the distribution board and creating the main equipotential bonding, the installation electrician faces heterogeneous downstream circuits. The absolute priority is to prevent a circuit that has not been made safe from compromising the safety of the renovated whole or from causing nuisance tripping of the new residual-current device (RCD). Each circuit retained must be examined methodically at the board before it is connected.
The recurring trap in buildings from the 1950s to the 1970s is the presence of neutral conductors shared between several overcurrent-protected circuits, as well as a mixture of conductors in threaded metal conduits or bitumen-impregnated cardboard. Before any re-energising via a 30 mA residual-current circuit breaker, individual identification of the neutral conductor and the corresponding phase is essential. If two separate phases share the same neutral, the residual-current circuit breaker trips as soon as load is applied. These circuits must then be grouped under a dedicated multipole circuit breaker or the secondary circuit locked out until it is completely rewired.
| Finding on the downstream installation | Risk level identified | Protective technical measure | Impact on operation |
|---|---|---|---|
| Sockets without protective contact (type 12) on a conductive floor | Direct or indirect electric shock in the event of an insulation fault | Connection downstream of a 30 mA residual-current circuit breaker at the board | Additional protection provided without immediate replacement of the wiring |
| Green-yellow protective conductor connected to the neutral downstream of the board (local TN-C system) | Dangerous potential on metal enclosures in the event of a neutral break | Neutral conductor and protective conductor must be separated at the board; circuit taken out of service if three conductors are not available | Socket or circuit taken out of service until the line is completely redone |
| Insulation resistance below the standard threshold between live conductors and earth | Overheating, fire risk in floors or permanent tripping | Disconnection of the circuit at the board, identification and fitting of an insulating cap on the strands | Circuit taken out of service and recorded on the operating diagram |
| Degraded textile sheath with insulation crumbling at the bottom of the box | Direct short circuit or accidental contact with a metal part | Circuit cut at the first sound box or insulated with heat-shrink sleeving | Partial supply maintained under monitoring and 30 mA RCD |
Lines that do not meet the minimum insulation requirements, or whose connections present a risk of overheating, must on no account be reconnected for the operator's convenience. The installer takes these circuits out of service by physically disconnecting the conductors at the terminal block of the distribution board, together with durable labelling stating the reason for the shutdown.
Discovery of pollutants, legal framework and written formalisation of the phasing
Work on old boards frequently leads installation personnel to handle supports made of asbestos cement, spark-arrester plates in screw-type fuse holders or braided textile gaskets. Likewise, cable penetrations sometimes pass through historic conduits containing asbestos materials. In these situations, the installation electrician must be able to recognise the hazard without carrying out any drilling, sanding or mechanical brushing without safeguards.
In accordance with art. 32 OTConst, if such a substance is found unexpectedly, work must be stopped and the client or their representative informed. The removal of these friable or degraded elements is a matter for a specialised, recognised firm. The electrician secures the area, locks out their workstation and documents the discovery for transmission to the site management.
To protect the company from any liability in the event of an accident on the portions not yet made safe, the contractual phasing cannot rely on oral agreements. A written stage record must be drawn up between the client and the installation electrician holding the installation permit. This technical document precisely delimits the scope of the work carried out, the list of final circuits neutralised because of obvious danger, and the agreed schedule for the later renovation phases.
Each stage completed leads to the updating of the single-line diagram and the circuit allocation table stuck inside the door of the enclosure. Temporary handwritten labels on adhesive tape are to be avoided: engraved or printed marking ensures that the occupant and later workers identify without ambiguity the circuit breakers supplying circuits awaiting rewiring. The electrician records in their works file the fault loop impedance measurements and the RCD tripping times taken during this transitional stage.
Managing blockages, work stoppages and responsibilities
During a staged refurbishment, opening old junction boxes or boards frequently reveals critical situations: conductors with crumbling tarred insulation, total absence of protective conductor continuity on wall sockets, or suspect thermal insulation. As soon as a direct risk of electric shock or abnormal overheating appears, the installation electrician cannot maintain the supply without incurring technical liability. In the face of a proven danger of injury or fire, the physical disconnection of the circuit concerned is required before any further work.
- Stopping when pollutant materials are foundIf asbestos cardboard conduits or suspect fire-stop panels appear around the main distribution board, all mechanical handling is prohibited. Under the Ordinance on Construction Work, work must be stopped and the client notified so that a diagnosis can be carried out and the treatment entrusted to a recognised asbestos-removal firm.
- Lockout in the event of client refusalIf the owner refuses to budget for making safe a critical section, the installer neutralises the faulty group. The fuse is removed or the circuit breaker padlocked under a danger label. This isolation prevents any unintended re-energising by the occupants of the building.
- Formal notification of dangerThe tradesperson writes a detailed notice reporting the risks found, in accordance with the contractor's duty to notify prescribed by the Code of Obligations (CO). This letter recommends prohibiting the use of appliances connected to the obsolete lines and documents the suspension of the work.
When the disagreement persists and blocks the execution of the staged plan, documentary rigour protects the company. The installer sends an interim measurement record detailing only the circuits accepted and declares the others out of service. If major defects persist without a correction accepted by the owner, the notice of defect rectification cannot be issued. Under the provisions of the OIBT governing the inspection of installations, the electrician sends a stage report notifying the owner of the non-conformities and, where applicable, warns the network operator in order to be released from any subsequent misuse.
Frequently asked questions
Can a 30 mA residual-current device be fitted on an old board without replacing the two-pole sockets without earth?
Yes, adding a 30 mA residual-current device upstream provides essential additional protection against indirect contact, even without a protective conductor. In the event of an insulation fault on a portable appliance, the residual-current device trips as soon as a leakage current passes through a person touching the casing. The NIBT allows this temporary improvement, but the next stage will require an earth conductor to be run and the two-pole sockets to be replaced by sockets with earth.
What document should be given to the client after only the distribution board has been made safe?
After the board has been replaced, the installer draws up the measurement record and the safety report relating exclusively to the renovated part. The document states explicitly that the rising mains and the downstream final circuits have not been modified. This stage document guarantees the compliance of the new switchgear and trip devices, while informing the owner that the old final lines will be checked during the later stages provided for in the renovation plan.
What should be done if the main equipotential bonding is non-existent in an old building?
Creating the main equipotential bonding is an absolute priority from the first renovation stage. The electrician must install a main earth busbar, connect the existing earth electrode or strip to it, then bond the metal water or gas pipes entering the building. Without this bonding required by the NIBT, the metal masses may spread dangerous potentials throughout the building in the event of an insulation fault.
How should old Bergmann-type metal conduits be handled when rewiring?
Old Bergmann tubes are often lined internally with bituminous cardboard that may contain asbestos. Before starting to pull in new insulated conductors, the installer checks the integrity of the conduit. If the tube is degraded, crushed or the insulation is crumbling into dust, the operation is stopped. Asbestos-removal work is a matter for specialised firms under the Ordinance on Construction Work. The electrician then prefers to install a new surface-mounted or embedded conduit to bypass the asbestos-containing passage.
Texts and standards cited
- OTConstOccupational safety requirements and stopping work when hazardous substances are unexpectedly found
- COContractor's duty to notify in the event of circumstances compromising safety or proper execution
- OIBTObligations to keep installations in good condition, inspect them and draw up safety reports
- NIBTTechnical rules for the design, installation and verification of low-voltage installations