🧱 CFC 215Corrosion protection and fire resistanceChapter 4 of 10 in the section

Measuring dry film thickness: where, how many points, and which value to retain

The durability of corrosion protection depends on compliance with the dry film thickness specified in the specifications. This chapter details the use of magnetic induction thickness gauges, measurement frequency based on surface area, the evaluation rule for minimum and average values, and the formal recording of results in an inspection report drawn up for the client.

Key takeaways

  • Dry film thickness directly determines the corrosion resistance of the steel structure.
  • Standard ISO 12944 defines the sampling plan and the minimum number of measurement points.
  • The 80/20 rule tolerates local deviations without compromising the overall compliance of the coating.
  • The measurement report validates technical acceptance and protects the contractor in the event of a dispute.

Equipment, calibration, and distribution of measurement points on steel profiles

Dry film thickness (DFT) inspection is carried out using an electronic thickness gauge operating on the magnetic induction principle on a ferromagnetic substrate. Prior to each inspection session on the construction site or in the workshop, the instrument must be adjusted on the original uncoated steel substrate, using non-metallic calibration shims of certified thicknesses close to the target value. This operation eliminates the influence of surface roughness resulting from blast cleaning.

The distribution of measurement points must not be done at random. The surface of the steel element is divided into separate inspection areas. The number of points depends directly on the total surface area of the structural steelwork component or the supported composite façade.

Minimum number of measurement points according to the inspected area (ISO 12944)
Area of the zone (m²)Minimum number of measurement pointsMaximum number of readings permitted without claim
Up to 1 m²5 pointsAll points are recorded
From 1 to 3 m²10 pointsCalculation of the average over 10 readings
From 3 to 10 m²15 pointsTargeted inspection on flanges and webs
From 10 to 100 m²30 pointsUniform distribution over the component

On rolled sections such as HEA, HEB, or IPE, each measurement point corresponds to the average of three individual readings taken within a circle of 15 millimetres radius. Measurements should be increased on singular areas such as flange edges, bolted connections, and fillet welds, as paint tends to pull away from sharp edges.

Acceptance rule for values and preparation of the inspection report

To declare a batch compliant, analysing the readings is not limited to comparing the overall average with the nominal dry film thickness (NDFT) required in the tender. Standard ISO 12944 imposes a strict tolerance rule regarding the acceptable minimum and maximum values on the structure.

  1. Verification of the overall averageThe average of all spot measurements taken over the inspection area must be greater than or equal to the specified nominal thickness (NDFT).
  2. Application of the 80% rule (minimum value)No spot measurement must be less than 80% of the specified NDFT. Any value below this threshold constitutes a major local defect requiring paint touch-up.
  3. Check of values between 80% and 100%Measurements between 80% and 100% of the NDFT are tolerated, provided they represent less than 20% of the total number of measurements taken on the area.
  4. Verification of the maximum thicknessThe maximum thickness must not exceed three times the NDFT (or the limit specified by the paint manufacturer) to prevent risks of cracking, blistering, or poor film tension.

The results must imperatively be recorded in a measurement report drawn up by the site foreman or the site manager. This document certifies the compliance of the protective system before closing up composite façades or integrating the elements into the structure. The report includes the designation of the parts, the brand and serial number of the gauge, the calibration date, the raw values recorded, the calculation of averages, and the acceptance decision. The contractor thus complies with their duty of care arising from the contract for work governed by the Code of Obligations (CO).

Sampling plan and distribution of points according to standard ISO 12944

Measuring dry film thickness (DFT or NDFT for Nominal Dry Film Thickness) is the only non-destructive inspection confirming the compliance of an anticorrosive or intumescent paint system applied to a steel structure. A local under-thickness compromises the barrier against moisture and chlorides, causing premature rust onset, while excessive over-thickness causes internal stresses, a risk of crazing, or impaired intumescent foam expansion during fire. The instrumentation is based on a magnetic induction thickness gauge for ferromagnetic substrates (S235, S355), calibrated beforehand on a prepared bare steel surface, combined with a certified standard plastic shim.

Standard ISO 12944 refers to the procedures in ISO 19840 to define the minimum sampling frequency on structural steelwork components. Measurements must never be taken at random: they are distributed across the entire element, paying particular attention to critical areas exposed to edge effects, such as flanges of IPE/HEB sections, trimmed edges, connection cut-outs, and weld seams. On a profile, each sampling point consists of an average of three to five spot readings taken within a radius of 20 millimetres.

Sampling grid for the number of measurement points based on the inspected area
Surface area of the inspection zone (m²)Minimum number of measurement pointsMaximum number of individual readings permitted below NDFT
Up to 1 m²5 points1 point
From 1 to 3 m²10 points2 points
From 3 to 10 m²15 points3 points
From 10 to 100 m²30 points + 10 points per additional 10 m² increment10% of total points

Decision rule for values and drafting the inspection report

To declare a painted surface compliant, the site manager or site foreman must apply the strict 80/20 rule from standards ISO 12944 and ISO 19840. The arithmetic mean of all individual measurements taken on the inspection area must be greater than or equal to the nominal dry film thickness (NDFT) specified in the specifications. No individual measurement may be less than 80% of the specified NDFT. If a value falls between 80% and 100% of the NDFT, it is tolerated provided that the quantity of these undersized points does not exceed 20% of the total measurements taken on the area.

In the event of non-compliance due to under-thickness, the defective area must undergo mechanical surface abrasion, followed by the application of a touch-up coat compatible with the listed system. If an out-of-tolerance over-thickness is found, levelling sanding down to the permitted limit value is required prior to final acceptance. The contractor satisfies their obligations regarding the quality of the material supplied pursuant to art. 365 CO by recording all execution checks in a quality assurance document.

  1. Batch identification and ambient conditionsRecord the reference of the profile or façade element, the date, the steel temperature, the ambient temperature, and the relative humidity measured during the inspection.
  2. Recording instrument dataRecord the thickness gauge model, serial number, calibration method performed on a certified shim, and the zero value adjusted on the bare substrate.
  3. Logging measurements and statistical calculationsEnter the individual values recorded per zone, calculate the overall average, identify the local minimum value, and verify the 80% rule.
  4. Verdict and dual signaturesExplicitly state the decision (compliant, to be corrected, or rejected) and have the inspection report signed by the application supervisor and site supervision.

Management of thickness non-conformities and corrective actions

During dry film thickness (DFT) inspection according to standard ISO 12944, any deviation from contractual requirements or manufacturer technical datasheets entails a rigorous analysis procedure before approval of the steel structure. When the average value of the inspection area is less than the prescribed nominal thickness (NDFT), or if a local minimum value drops below the tolerated limit of 80% of the NDFT, the steel element cannot be accepted as is. Likewise, excessive over-thickness, frequent around connection nodes and weld beads, poses a major risk of cracking, loss of adhesion, or solvent entrapment.

  1. Treatment of local or general under-thicknessIn the event of insufficient thickness, dedusting and surface sanding are required to create a minimum mechanical key. A compatible additional coat is then applied to achieve the target NDFT. If the maximum overcoating interval specified by the manufacturer is exceeded, complete mechanical keying of the previous coat is mandatory.
  2. Treatment of critical over-thicknessIf the measured thickness exceeds the allowable ceiling established by the system (often three times the NDFT for conventional anticorrosive paint, or the maximum limit specified for an intumescent fire protection system), the area must be removed by light grinding or sanding down to within tolerances, then reapplied.
  3. Formalisation in the measurement reportAny correction is recorded precisely in the report. Corrected areas undergo a series of supplementary measurements at the same location. The rights of the client in the event of defects are governed by art. 368 CO, requiring written traceability of the rectification.

Frequently asked questions

What should be done if an individual thickness measurement drops to 75% of the NDFT value?

According to the rules of standard ISO 12944, no individual value must be less than 80% of the nominal dry film thickness (NDFT). An isolated value at 75% constitutes a local non-conformity. The number and distribution of measurement points around this area should be checked. If the defect is confirmed, surface sanding and local paint touch-up are required.

How should measurement points be distributed on a complex welded plate girder?

For complex structural steelwork components, the sampling plan divides the part into distinct inspection areas: flanges, webs, gussets, and weld zones. The number and distribution of points must cover all faces. On sharp edges and welds, measurements are stepped up because paint shrinkage frequently reduces the dry film thickness there.

Why is the average of measurements not sufficient to validate a batch of structural components?

A compliant average can conceal a critical severely under-thickness area beneath which the steel will rust prematurely. The acceptance rule requires two cumulative conditions: the overall average value must be equal to or greater than the specified NDFT, and every local minimum value must comply with the 80% threshold. It is this dual condition that guarantees durable corrosion protection for ten years or more.

What minimum information must appear on the thickness measurement report?

The measurement report records the component designation, the date, ambient temperature, relative humidity, the instrument used, and its shim calibration. It details the number and distribution of points, individual values, the local minimum value, and the calculated average. This official document, signed by the inspector, is mandatory for works acceptance and the validation of corrosion protection warranties.

Texts and standards cited

  • ISO 12944Paints and varnishes - Corrosion protection of steel structures by protective paint systems
  • CO art. 368Rights of the client in case of defects in the work