Hydraulic distribution and balancing: the execution reference

Intended for heating team leaders and foremen, this section brings together the methods for calculating, setting and checking hydraulic distribution. From the boiler room to the last emitter, it covers the sizing of closed networks, circulator control, water quality and methodical balancing to guarantee the design flow rate at every floor in accordance with SIA 384/1 and the Suissetec guidelines.

  • 10chapters
  • 22 000words
  • 6sections in the training course
  • 60chapters in total

Key values to remember 4

Suissetec guideline

0.5 to 1.0 m/s

Recommended flow velocity in main risers

Norme SIA 384/1

1.3 times

Minimum hydraulic test pressure relative to the operating pressure

Norme SIA 384/1

< 100 Pa/m

Target linear pressure loss to limit noise and pumping power

Norme SIA 384/1

0.5 bar

Absolute minimum pressure at the highest point of the installation

Technical scope of the hydraulic network and construction site interfaces

Hydraulic distribution is the backbone of every thermal installation. It covers the transport of heat energy from the production unit to the emission terminals through a closed-circuit network. For the heating fitter, the operational objective is to deliver the heat-transfer fluid at a precise flow rate, with controlled pressure loss and no noise nuisance whatsoever, while proving the conformity of the installation at acceptance.

Respecting the interfaces guarantees the overall quality of the works and limits disputes at handover. Under art. 364 CO, the contractor is responsible for the proper and faithful execution of the work entrusted to them. On the heating construction site, this means supplying correctly sized pipework that is leak-free, vented, balanced and insulated in accordance with the recognised rules of the art.

Allocation of responsibilities at the technical interfaces of the distribution system
Installation elementCFC 241 responsibility (Heating)Third-party interface
Filling disconnectorConnection to the heating circuitInstallation of the disconnector on the drinking-water supply (CFC 250)
Underfloor heating beneath screedLaying of pipes and manifolds and pressurisationEmbedding, expansion joints and moisture check (CFC 281)
Electrical distribution cabinetConnection of circulators to the boiler room terminal blockSupply line and main circuit breakers (CFC 232)
Ventilation duct coilsFlow/return pipework and control valvesAir handling unit and air distribution network (CFC 244)

Sequential methodology: from rough installation to the acceptance record

The execution of a hydraulic network leaves no room for improvisation. An imbalance on one riser inevitably leads to excess pump consumption, whistling at thermostatic valves and complaints about lack of comfort on the upper floors. The chapters of this section should be consulted in the actual order in which the work progresses on the construction site.

  1. Design and geometric layout (J3-01 and J3-09)Start by setting the pipe diameters according to the mass flow rates and the permissible pressure losses, allowing in advance for fixed points and free sliding to absorb thermal expansion without causing creaking.
  2. Integrity check and mechanical safety (J3-02 and J3-07)Before any insulation is applied, the network undergoes a water-pressure leak test documented in writing, while the pressure-maintaining unit and the safety valve are calibrated accurately.
  3. Conditioning of the heat-transfer fluid (J3-06)Filling must always be carried out with demineralised or softened water complying with the recommendations of the trade, preventing early scaling and the formation of destructive magnetite sludge.
  4. Hydraulic setting, pumping and insulation (J3-03, J3-05 and J3-08)The electronic circulators are adjusted to the correct characteristic curve. The balancing valves at the riser base and at the distributors are throttled to the setpoint values read on the differential pressure gauge, before the thermal insulation shells are closed.
  5. Final inspection and energy metering (J3-04 and J3-10)In the event of a complaint about under-heating at the end of a branch, a step-by-step diagnostic method rules out air-flow and mechanical pitfalls, complemented by the metrological verification of the individual heat meters.

Every thermal distribution network must undergo documented hydraulic balancing to guarantee the nominal flow rates at full load and at partial load.

Suissetec guideline

By applying this step-by-step approach, the site foreman ensures that the commissioning record is based on measured, indisputable physical quantities, eliminating costly rework after the tenants have moved in.

📘 Chapters in this section 10

Hydraulic distribution and balancing

Sizing pipework: flow rate, velocity, pressure drop and flow noise

Master pipe-section calculations to eliminate whistling and reduce pumping power.

Hydraulic distribution and balancing

The hydraulic pressure test: test pressure, duration, permitted pressure drop and test report

Secure your acceptance inspections with an impeccable, undisputed pressure test protocol.

Hydraulic distribution and balancing

Balancing properly: flow rate calculation, balancing valves and recorded readings

Adjust the control valves to the actual values to guarantee comfort on every floor.

Hydraulic distribution and balancing

Three degrees colder on the top floor: the diagnosis, step by step

Quickly identify the exact cause of a lukewarm radiator without needlessly raising the heating curve.

Hydraulic distribution and balancing

Setting the circulator: curve, differential pressure and power consumption

Select the optimal control mode to halve the electricity consumption of the pumps.

Hydraulic distribution and balancing

Circuit water: hardness, magnetic sludge, corrosion and treatment

Protect the heat exchangers against scaling and sludge through rigorous water conditioning.

Hydraulic distribution and balancing

The expansion vessel: volume, pre-charge pressure and safety valve

Calculate the useful volume and the pre-charge pressure to avoid nuisance tripping of the safety valve.

Hydraulic distribution and balancing

Insulating pipework: thicknesses, singular points and losses in unheated rooms

Insulate pipework and fittings in the boiler room in accordance with the cantonal legal energy-efficiency requirements.

Hydraulic distribution and balancing

Let it move: expansion, fixed points, sliding supports and creaking noise

Arrange fixed and sliding clamps to absorb expansion without transmitting structure-borne noise.

Hydraulic distribution and balancing

Metering per dwelling: meter position, accuracy and disputes

Install and connect heat meters without disturbing the metrology or distorting the billing.