🧱 CFC 272Wall coverings: wallpaper and wall hangingsChapter 7 of 10 in the section

Damp room: suitable wall covering, condensation behind it, and what we refuse to install

This chapter enables you to identify configurations at risk of interstitial condensation when installing a wall covering in a damp room. You will be able to assess the thermal impact of uninsulated walls, check the air-renewal conditions, draft a reasoned written refusal in response to non-compliant requests and specify a durable technical solution.

Key takeaways

  • Installing an impermeable vinyl on an uninsulated cold wall inevitably produces concealed mould.
  • The absence of a functioning controlled mechanical ventilation system justifies the systematic refusal of any heavy decorative covering.
  • The water vapour permeability of the adhesive-and-covering build-up determines the healthiness of the wall.
  • A formal written notice relieves the painter of liability while proposing viable mineral alternatives.

Understanding the condensation trap behind impermeable coverings

In poorly insulated wet rooms or rooms subject to high humidity, the choice of a covering does not depend solely on its appearance or surface cleanability. The most frequent mistake is to install a waterproof vinyl wallpaper on a cold exterior wall, in the belief that its plasticised surface will protect the substrate from splashes. In reality, a compact wall covering acts as a vapour barrier placed on the wrong side of the wall. The water vapour generated by showers or washbasins passes through the joints between the strips, the gaps at skirting boards and the technical penetrations, then reaches the cold surface of the supporting wall.

Dew point on the underside
Critical temperature at which humid air cools on direct contact with the uninsulated masonry substrate, causing the vapour to change state into liquid water trapped directly behind the waterproof membrane of the wall covering.

When the wall's surface temperature drops below the dew point, liquid water accumulates in the adhesive bed. Traditional adhesives based on methylcellulose or starch undergo rapid hydrolysis and lose all mechanical bonding strength. This causes blistering, spontaneous lifting of the edges, then massive development of black fungal spores invisible from the room. The smell of mould appears well before the vinyl is visibly perforated. The diffusion of water vapour is blocked by the polyvinyl chloride layer, preventing the wall from drying towards the interior space.

Behaviour of coverings in a humid atmosphere according to permeability
Type of coveringVapour permeabilityBehaviour on a cold wallPermissible use
Compact vinyl wallpaperPractically nilTotal water entrapment, adhesive rotDry rooms only
Glass fibre fabric + acrylic finishModerate to goodSlow moisture release if a suitable adhesive is usedVentilated kitchen, circulation areas
Breathable non-woven without PVC coatingHighSteady drying without retention, provided there is ventilationBathroom with continuous controlled mechanical ventilation
Textile wall coveringVery high but absorbentWater soaking, staining, rapid deteriorationExcluded in damp environments

Setting the technical conditions, refusing in writing and proposing the alternative

Before accepting the installation of a covering in a bathroom, the team leader carefully checks the air conditions. A controlled mechanical ventilation system in continuous operation is the absolute prerequisite for keeping relative humidity below the critical thresholds. A simple tilt-and-turn window or a passive grille is not enough to ensure the air is kept healthy in winter. If the room has no forced extraction ensuring rapid removal of humidity peaks, the installation of any bonded decorative covering must be ruled out without compromise.

  1. Checking exposure and ventilationCheck whether the wall faces the exterior and assess its thermal inertia. Make sure a functioning air extractor with sufficient flow rate is present.
  2. Drafting the formal written noticeImmediately notify site management in writing that the requested impermeable covering is unsuitable, given the certain risks of lifting and mould.
  3. Formulating technical variantsPropose as a replacement a microporous paint finish or a breathable system specifically formulated for rooms with high vapour production.
  4. Awaiting formal approvalDo not carry out any application without a joint written instruction from the agent or acceptance of the change to the tender.

The obligation to notify the client derives directly from the rules of the contract for work and services under the Code of Obligations (CO) and the SIA 118 standard. A painter-contractor who accepts without reservation to apply an impermeable material on a substrate exposed to condensation incurs full civil liability in the event of subsequent damage. The written notice must clearly set out the cause-and-effect link: the airtight nature of the ordered finish, the temperature gradient between interior and exterior, moisture saturation and the inevitable failure of the adhesive film.

  • Formally prohibit vinyl fabrics and waterproof plasticised coverings in the immediate protection zones of showers and bathtubs.
  • Use exclusively adhesives reinforced with synthetic resins treated against micro-organisms for the permitted permeable coverings.
  • State in the notice of defects the health risks linked to the development of pathogenic spores confined behind the strip.
  • Record the residual moisture of the substrate and the ambient temperature in the site diary on the day of the work.

Surface diagnostics and verification of ventilation before installation

Installing a wall covering in a damp room requires prior, instrument-based verification of the thermo-hygrometric balance. A visual check is never enough to guarantee the durability of the build-up. The team leader systematically measures the relative humidity of the ambient air, the ambient temperature and the contact temperature of the wall using a thermo-hygrometer combined with a surface contact thermometer. Comparing these values immediately gives the dew point temperature.

When the surface temperature of the masonry comes within three degrees of the calculated condensation temperature, all bonding must be suspended. This situation arises almost systematically on walls facing the exterior in older buildings without external thermal insulation, or at structural thermal bridges such as reinforced concrete slab edges. The humidity of the indoor air then saturates the substrate as soon as vapour production in the room increases.

On-site decision matrix according to the thermal state of the wall and ventilation
Wall configurationRoom ventilation regimeHygrothermal riskExecution decision
Exterior wall without thermal insulationIntermittent natural ventilation (window only)Major interstitial condensation behind any waterproof coveringFormal refusal of any vinyl or film-forming covering
Insulated exterior wall (contemporary standard)Functioning controlled mechanical extractionLow risk if the dew point remains within the insulationCovering with controlled permeance permissible
Heated interior partitionVerified permanent mechanical extractionVirtually no risk outside areas of direct splashingInstallation permitted with reinforced water-repellent adhesive
Concrete wall in basement or lower ground floorNo mechanical extraction in operationContinuous capillary saturation and underlying mouldStop work until the controlled mechanical ventilation is commissioned

The existence and effective operation of mechanical ventilation is a condition precedent for the decorating work on the construction site. The painter checks the suction flow at the extraction grille using a vane anemometer or a test sheet held in place by the negative pressure. If the collective ventilation is switched off for works or if the extraction ducts are blocked, the contractor sends a notice of interruption to site management. Installing any covering in an unventilated bathroom directly engages the technical responsibility of the applicator in the event of accelerated rotting of the adhesives.

Substitute microporous build-ups and installation protocol

To meet the client's aesthetic requirements while safeguarding the healthiness of the structural work, the technical alternative relies on materials with high water vapour diffusivity. The water-vapour diffusion-equivalent air layer thickness, known as the Sd value, must remain below 0.1 metre. Preference is given to pure woven glass fibre fabrics or uncoated cellulose-polyester non-wovens, free of PVC coating. These structures allow the wall to absorb a fraction of moisture during production peaks and then release it fully as soon as ventilation dries the air.

  1. Fungicidal decontamination and breathable sealingWash the masonry with a detergent solution and rinse with clean water. Then apply a water-based biocide treatment to neutralise residual spores. After complete drying, apply a bonding primer based on a microporous water-soluble resin to even out absorption without closing the surface.
  2. Application of a specific moisture-resistant adhesiveUse an adhesive for heavy wall coverings free of pure starch, enriched with dispersed synthetic resins and containing antifungal preservatives. Apply the adhesive by roller directly onto the wall at approximately two hundred to two hundred and fifty grams per square metre, without excess thickness that would create pockets of water.
  3. Hanging the non-woven or glass fibre fleeceHang the breathable non-woven strips edge to edge, smoothing from the centre towards the edges with a flexible plastic spatula to expel air bubbles. Avoid stretching the textile weave to prevent shrinkage on drying.
  4. Finishing with vapour-permeable paintApply two cross-coats of matt or velvet emulsion paint classified as microporous, containing surface fungistatic agents. Strictly avoid polyurethane lacquers or epoxy resins, which would recreate an impermeable film on the surface.
  5. Elastomeric perimeter sealingSeal the junctions at internal corners, skirting boards and door frames with a neutral elastomeric sealant based on fungicidal silicone, to prevent any capillary infiltration of running water under the edge of the covering.

Where a structurally cold wall persists with no possibility of remediation through the exterior envelope, the painter formalises the refusal in accordance with SIA 118 and proposes the outright abandonment of any textile or wallpaper. The fallback technical solution is then a mineral potassium silicate paint system applied directly onto stripped mineral render, ensuring maximum permeance while biologically neutralising the substrate through its natural alkalinity.

Condensation damage: lifting, concealed mould and handling the refusal

The discovery of widespread blistering, clean lifting at the edges or blackish stains along the skirting boards signals the complete failure of the finishing system. When a waterproof covering such as heavy vinyl has been applied to an uninsulated wall facing the exterior, the ambient water vapour passes through the micro-openings at the joints, condenses on contact with the cold masonry wall and remains trapped behind the impermeable plastic sheet. The organic adhesive degrades through saponification and biological rotting, releasing fungal spores under the strip.

  1. Complete removal and stripping of the substrateStrip off the entire impermeable covering without trying to preserve apparently sound areas. Meticulously remove the pasty adhesive residues by scraping and washing down to bare plaster or concrete.
  2. Remediation and curative fungicidal neutralisationApply a certified mould destroyer free of residual chlorine, brush vigorously, then rinse with a clean, wrung-out sponge. Leave to take effect according to the supplier's instructions before deep drying by mechanical ventilation.
  3. Air-flow audit and humidity checkMeasure the moisture content by mass of the substrate and check the effectiveness of the stale-air extraction system. If the hourly air change rate is insufficient or nil, record the physical incompatibility of the room in the site report.
  4. Written refusal and technical redirectionFormally notify the client that the durability of a blocking covering cannot be guaranteed. Submit an alternative offer providing for a microporous mineral build-up that is open to diffusion.

Under the recognised rules of the profession and the duty to notify defined by SIA 118, the painter must record his technical reservations in writing as soon as the defects occur. If site management refuses to correct the thermal bridge in the façade or to provide continuous air extraction, the company must suspend execution on the disputed substrate. Lasting restoration excludes any return to waterproof finishes and requires the application of mineral silicate paints or a microporous fleece open to diffusion.

Frequently asked questions

Can vinyl wallpaper be installed in a bathroom if it has a window?

The presence of a simple window does not guarantee constant removal of the water vapour generated by showers, particularly in winter when ventilation remains brief. If the vinyl is installed on a wall in contact with the exterior or an unheated room, the thermal shock causes interstitial condensation behind the waterproof sheet. Without permanent mechanical extraction ensuring a controlled air flow, the installation of vinyl must be ruled out in favour of a microporous covering.

How should one react contractually if the client insists on keeping a waterproof wallpaper despite the risk?

In accordance with the duty to notify under SIA 118, the painter records his refusal in writing, detailing precisely the foreseeable condensation and mould mechanisms. If the client maintains his order despite the technical warning, the contractor must demand a signed formal release from liability or refuse to carry out the work. Knowingly installing an unsuitable system on a cold wall exposes the contractor to bearing the cost of repairing future damage in the event of a claim.

What water vapour permeability value should be required for a covering in a damp room?

To prevent the accumulation of liquid water behind the covering, the vapour diffusion resistance value, expressed as the equivalent air layer thickness Sd, must remain below 0.1 metre. Glass fibre fabrics or paintable cellulose non-wovens combined with microporous acrylic paints or silicates meet this openness requirement. Conversely, expanded or compact vinyls have very high Sd values, creating a sealed barrier conducive to lifting on a cold wall.

What durable aesthetic alternative can be proposed to the client instead of vinyl?

The most robust alternative is to apply a breathable glass fibre or cellulose-polyester renovation fleece, coated with a washable class 1 satin acrylic paint or a water-based polyurethane resin. In zones directly exposed to running water, a mineral decorative render that is impermeable to liquid water but permeable to vapour is an advantageous replacement for wallpaper. This combination preserves the desired decorative appearance while ensuring continuous hygrometric remediation of the masonry.

Texts and standards cited

  • norme SIA 118General Conditions for the execution of construction work, the contractor's duties to notify and to warn