Key takeaways
- The reinforcing mesh must absolutely be located in the upper third of the base coat.
- A mesh pressed directly against the insulation cancels the reinforcing effect and causes shrinkage cracking.
- The longitudinal and transverse overlap between two mesh strips is at least ten centimetres.
- The diagonal strips at opening corners are always applied before the full-width strips are laid.
Positioning of the reinforcing mesh within the thickness of the base coat
On rendered external thermal insulation, the base coat provides the mechanical strength of the system against hygrothermal stresses and impacts. According to the rules of the trade and the application guidelines of the SIA 243 standard, the glass-fibre mesh acts as a tensile reinforcement, comparable to steel reinforcement in reinforced concrete. Its effectiveness depends entirely on its embedment and its depth within the base coat layer.
- Outer third of the plaster
- Zone of mechanical action located in the first third of the total thickness of the base coat, counting from the outer face. For a 4 mm base layer, the reinforcement must lie between 1.3 mm and 2.5 mm below the finished surface of the reinforcing coat.
- Applying the first coat of mortarSpray or apply the bonding and reinforcing mortar with a notched steel trowel onto the dust-free insulation boards. Spread the layer to deposit at least two thirds of the final thickness specified by the system.
- Embedding the mesh without creasesLay the glass-fibre mesh strip into the still-fresh mortar. Press gently with the flat of the smooth trowel, working from the centre towards the edges, never stretching the mesh or pushing it in so far that it touches the insulation.
- Embedment and surface smoothingImmediately apply the closing coat wet-on-wet to fully cover the mesh grid. No thread must remain visible or show in relief on the finished surface before complete drying.
| Type of base coat | Nominal thickness | Target mesh depth | Site check |
|---|---|---|---|
| Thin mineral or organic plaster | 3 to 4 mm | Outer third (minimum embedment 1 mm) | Mesh not visible but perceptible under 1 mm of mortar |
| Medium or heavy plaster | 5 to 8 mm | Half to outer third | Check with a thickness gauge on fresh mortar |
| Reinforced plaster with double reinforcement | 7 to 10 mm | Heavy mesh at the bottom, standard mesh in the outer third | Check of the two separate coats with intermediate drying |
Strip overlaps and diagonal reinforcements at façade openings
The continuity of tensile force transmission depends on the precision of the joints between mesh strips. In accordance with the SIA 243 standard, the connection between two successive reinforcement strips requires a minimum overlap of 100 mm, both vertically and horizontally. The manufacturers' prefabricated selvedges generally mark this zone with a coloured line. A break in the overlap or a simple butt joint of two raw edges creates a line of weakness where the plaster splits at the first freeze-thaw cycle.
The textile reinforcement must be completely embedded in the reinforcing mortar, have a continuous overlap between the individual strips and include the necessary reinforcements at stress concentrations, in particular at the corners of openings.
Norme SIA 243
The corners of glazed openings, windows and doors concentrate the shear stresses caused by temperature variations and settlement of the structure. If only the standard strip is laid, a crack at 45 degrees systematically starts from the edge of the frame and spreads across the façade. Installing corner reinforcements, commonly called patches, neutralises this diagonal deformation.
- Patch dimensions: rectangular mesh strips cut to minimum dimensions of 300 mm by 500 mm (or 250 mm by 400 mm according to the manufacturer's recommendations).
- Orientation: laid strictly at 45 degrees to the window jambs and lintels, as close as possible to the corner of the subframe or rebate.
- Bonding sequence: the diagonal patch must be pressed into the first coat of mortar before the general full-wall mesh is laid.
- Reinforced corner beads: systematic use of PVC angle beads with integrated mesh wings of at least 100 mm on the external edges of the reveals.
- No joint crossing: the joint between insulation boards must never lie in the exact extension of an opening corner, otherwise the reinforcement is ineffective against thermal movement.
Positioning in the outer third and execution of overlaps
In an external thermal insulation system (ETICS/render on insulation), the reinforced base coat provides both rainwater tightness and mechanical resistance to hygrothermal stresses. Sudden variations in sunshine and temperature induce considerable tensile stresses at the surface of the base layer. If the glass-fibre reinforcement is laid directly against the insulation board, it ends up in the neutral or compressed zone of the mortar thickness: its effectiveness against surface tension is nil, which causes generalised crazing and then through-cracks.
In accordance with the rules of the trade and the SIA 243 standard, the textile mesh must absolutely be located in the upper third of the plaster mass, while remaining fully embedded by at least 1 mm of mortar to avoid detachment or degradation caused by alkalis. The reinforcement must on no account be visible after floating. The total thickness of the reinforcing layer generally varies from 3 to 5 mm for fine mortars, and reaches 5 to 8 mm for thicker mineral mortars.
- Applying the first coatSpray or spread the reinforcing mortar with a notched trowel (8 to 10 mm teeth) onto the dust-free insulation boards, to a thickness of about two thirds of the final coat.
- Pressing in the meshUnroll the mesh from top to bottom and embed it in the fresh mortar using a stainless steel float, without stretching it or creating waves, from the centre towards the outer edges.
- Methodical overlapping of stripsMaintain a systematic overlap of 100 mm between two consecutive strips, on both vertical and horizontal joints. Avoid any superposition of four layers at the same crossing.
- Smoothing and covering wet-on-wetImmediately apply the second coat of mortar (the remaining third) to saturate the mesh and obtain a flat surface, without waiting for the lower coat to start setting.
Diagonal reinforcements at openings and treatment of edges
The corners of openings (windows, doors, recesses) are critical points subject to very high concentrations of shear stress. Without precautions, characteristic oblique cracks at 45 degrees appear from the first freeze-thaw cycles or strong summer sunshine. To neutralise these lines of failure, the installation of diagonal reinforcing patches is required by the SIA 243 standard before or during the laying of the general mesh layer.
These cut rectangular pieces of mesh (usual dimensions from 250 x 400 mm to 300 x 500 mm) are inserted directly into the fresh plaster as close as possible to the internal corner of the opening. The diagonal of the piece must exactly extend the imaginary line of the corner of the opening. In reveals and lintels, corner profiles with an integrated mesh flap must also overlap by 100 mm with the returns of the façade reinforcement to guarantee the continuity of the mechanical reinforcement.
| Defect observed | Execution cause | Corrective measure on site |
|---|---|---|
| Cracks at 45° at window corners | Diagonal patch omitted or piece cut too small | Apply a patch of at least 250 x 400 mm pressed in at 45° at the edge |
| Regular ghosting of the mesh on the surface | Mesh laid too close to the outside without embedment | Ensure a minimum of 1 mm of mortar above the glass fibre |
| Straight vertical cracks spaced 1 m apart | Insufficient overlap between strips (edge to edge) | Require the gauge line or 100 mm of continuous overlap |
| Detachment of the finishing coat | Mesh applied dry on the insulation (no binder behind) | Execution wet-on-wet: 2/3 for the base coat, pressing in, 1/3 for the surface |
Diagnosis of reinforcement defects and repair protocols
When the base coat shows microcracks or early crazing, the first step is to take a core sample or make a local test window of ten centimetres per side. This sample makes it possible to check the total thickness of the base layer and the exact position of the glass fibre. According to the SIA 243 standard, the reinforcement must absolutely be located in the upper third of the coat, embedded by at least one millimetre of mortar on its outer face. If the mesh is pressed directly against the insulation or bonded without a prior bed of mortar, the work absorbs no shrinkage tension and the risk of structural cracking becomes systematic.
Where the mesh has been laid too deep or the overlaps between strips are insufficient (below the required ten centimetres), simple surface bridging remains ineffective. If the plaster is hardened but the finishing coat has not been applied, the technical solution consists of lightly sanding the surface to open the grain, dusting it off carefully, then reapplying a complete base coat of about three millimetres reinforced with a new mesh pressed in according to the rules. In the event of a defect discovered after handover, the client's rights for construction defects are exercised in accordance with the provisions of art. 368 CO, requiring rectification at the contractor's expense if the stability of the envelope is compromised.
For the typical diagonal cracks at opening corners caused by the omission of reinforcing patches, the repair requires targeted removal. The façade contractor grinds the base coat over an area of about fifty by fifty centimetres around the edge, in a bevel and without cutting into the underlying insulation board. A glass-fibre mesh patch of two hundred by four hundred millimetres is then embedded at forty-five degrees in a new coat of bedding mortar, ensuring a continuous peripheral overlap of at least ten centimetres with the existing reinforcement retained around the edge.
Frequently asked questions
What to do if the mesh has been pressed directly against the insulation board?
This defect deprives the system of its mechanical absorption capacity. A mesh pressed to the bottom is subject to no tensile stress and promotes delamination. If the plaster is fresh, the sheet must be removed immediately, the base mortar applied, the surface combed, then the mesh repositioned in the outer third. On hardened plaster, a complete second reinforced base coat is mandatory before considering the finishing coat.
What is the minimum overlap width required between two reinforcement strips?
The SIA 243 standard sets the minimum overlap between strips at ten centimetres on standard surfaces. This value guarantees the continuous transfer of the tensile forces created by temperature swings. A simple juxtaposition without overlap or an overlap reduced to a few centimetres creates a continuous line of weakness. A straight linear crack will then inevitably appear in the finishing render at the exact location of the non-conforming joint.
Why do opening corners systematically crack without a diagonal reinforcement?
The corners of window and door openings concentrate dynamic shear stresses and the differential shrinkage of the masonry. The vertical or horizontal mesh laid over the full wall area cannot neutralise these oblique lines of failure. The prior embedding of reinforcing patches cut at forty-five degrees spreads these stresses. Without these bevelled pieces of minimum dimensions of twenty by forty centimetres, the crack spreads outwards.
How to treat a crack that has appeared at a window corner after complete drying?
Simply filling the crack at the surface is out of the question. The façade contractor must open up the plaster with an abrasive disc in a bevel over fifty centimetres around the crack, without cutting into the insulation. After dusting, he applies a coat of bedding mortar, embeds a reinforcing patch at forty-five degrees ensuring ten centimetres of overlap onto sound plaster, then levels it before locally redoing the floated finish.
Texts and standards cited
- SIA 243Installation of rendered external thermal insulation systems and reinforcement requirements
- CO art. 368Client's rights in the event of defects in the work: rectification, price reduction or termination