🧱 CFC 274Balustrade loads and sizingChapter 7 of 10 in the section

Solid infill: wind exposure, additional load and exposed balcony

This chapter gives you the method for including the wind load on a solid balustrade in sheet metal or glass. You will be able to calculate the exposed area, assess the influence of altitude or site according to SIA 261, combine wind and service thrust, then adapt the section of the posts and the anchorage.

Key takeaways

  • A solid infill turns the balustrade into a full screen facing suction and pressure.
  • SIA 261 sets the wind pressure according to altitude and topography.
  • The metalworker must combine the action of the wind with the horizontal service thrust on the handrail.
  • The increased force at the post base requires rigorous design of the shoes and anchorages.

The sail effect turns the dynamic wind pressure into a major load on the balustrade

In a traditional balustrade with rails or vertical balusters, air flows through the gaps: wind exposure remains marginal compared with the horizontal service load. As soon as the project specifies a solid infill, made of steel or aluminium sheet panels or laminated safety glazing, the element acts as a continuous screen. The structure captures the entire air flow, generating considerable surface forces perpendicular to the plane of the balcony. This aerodynamic stress is immediately transferred to the secondary structure: glass clamps, glazing beads, tubular posts and anchor plates.

Sail effect
Mechanical behaviour of a solid metalwork element that intercepts air without permeability, turning the dynamic wind pressure into a full surface thrust transferred to the anchor connections.

SIA 261 defines the reference dynamic pressure as a function of the geographical location and altitude of the project in Switzerland. On the Swiss Plateau, the base pressure is moderate, but it rises as soon as the construction site moves into the Jura, the Pre-Alps or the Alpine valleys. To this value is added the direct influence of the roughness of the surrounding terrain: a balcony in a dense urban area benefits from favourable roughness that slows gusts, whereas a structure on the shore of Lake Geneva, on an open plateau or on a ridge is subject to direct turbulence and increased pressure coefficients.

Comparison of loads on a balustrade according to the type of infill (height 1.00 m)
Type of infillPermeability to air flowTransmission of the wind loadPredominant force for the fixings
Open vertical balustersHigh (regular gaps greater than 80%)Negligible over the overall surfaceHorizontal service thrust on the handrail
Perforated sheet (voids greater than 50%)Medium (partial attenuation of the flow)Intermediate, depending on the drag coefficientMixed, depending on the exposure of the building
Solid sheet or laminated glassNone (fully opaque or transparent screen)Full dynamic load according to SIA 261Combination of unfavourable wind and service thrust

The calculation of the area exposed to wind must include not only the sheet or glass, but also the geometry of the lower closing flashings and the developed length of the handrail. On a continuous balcony, building-corner effects create locally accentuated suction that is often twice as severe as simple frontal overpressures. The metalworker must therefore design the framework to resist symmetrically, towards the inside as well as the outside of the balcony.

The combination of loads and the exposure of the site dictate the anchorage and the moment of inertia of the posts

On an exposed balcony, structural safety rests on the superposition of loads. In accordance with the principles of SIA 261, the design of a balustrade with solid infill cannot be limited to checking the resistance to the service thrust of people (generally applied horizontally on the handrail). The service load and the wind load must be combined according to the combinations of actions appropriate to the ultimate and serviceability limit states, taking into account the simultaneity factors defined by the rules of the trade.

For the metalworker, the effect of this combination is immediately apparent on two critical components of the work:

  • The section modulus and moment of inertia of the posts: a square tube or standard flat bar sized for balusters deflects excessively under the wind on a solid panel, risking breaking the laminated glass or buckling the sheet.
  • The anchorage in the concrete: the tensile force on the fixing anchors increases from single to triple in the event of strong combined wind on a balcony at height.
  • The intermediate attachments: the glass clamps and sheet fixing brackets must resist shear and pull-out without slipping of the elastomer seals.
  • The overall stiffness: the deflection at the top of the balustrade under gusts must remain limited to preserve the user's sense of safety and avoid cracking.

Installing a solid balustrade on a balcony therefore requires precise coordination with the designer or the civil engineering office. The metalworker collects the wind assumptions for the site: exact altitude of the building, wind zone, height of the balustrade above natural ground and terrain category according to SIA 261. When the fixing is made to the slab edge rather than on top of the slab, the lever arm increases further: the vertical plates require reinforced steel thicknesses and certified mechanical or chemical anchors, with sufficient spacing to avoid spalling of the concrete edges.

Calculation of the exposed area and exposure factors according to SIA 261

For the metalworker, the assessment of the area exposed to wind is not limited to the gross area of the balcony. A balustrade incorporating laminated safety glazing or a solid aluminium sheet panel turns an open edge into a continuous, airtight wall. SIA 261 requires the peak dynamic pressure to be determined according to the geographical location of the structure, its altitude above sea level and the local topography. In an Alpine environment or on the pre-Alpine ridges of the Jura and the Fribourg Pre-Alps, the reference value of the pressure increases rapidly with altitude. A structure installed at 1200 metres above sea level is subject to markedly more severe base forces than a similar balustrade installed on the shores of Lake Geneva.

The terrain category directly influences the wind speed profile. In open country or right on the edge of a large body of water (roughness category without obstacles), the wind strikes the façade with maximum kinetic energy, without damping by the built environment. In a dense urban area, the turbulence is more complex but the mean speeds are slowed by the surrounding obstacles. However, building-corner effects and flow separation create local pressures and suction that are often greater than the direct thrust. For a corner balcony on a penthouse, the external pressure coefficient reaches critical peaks that overload the inner or outer face of the infill panel.

Influence of the site and the panel type on the aerodynamic load
Infill configurationTerrain roughness categoryDominant aerodynamic effectDirect impact on the framework
Continuous laminated glass without gapLakeside or open plainAbsolute sail effect, leeward suctionMaximum torsional couple and overturning moment
Solid sheet riveted to postsUrban or peri-urban areaCorner turbulence and lateral suctionDynamic loading of the intermediate fixings
Perforated sheet (voids greater than 30%)Any exposure zonePartial permeability reducing dragAppreciable reduction of the forces at the base of the posts
Clamped glass with 100 mm bottom gapExposed penthouse or windy ridgeAir release at floor level, local reliefMarginal reduction of the total thrust but water clearance maintained

The net area subjected to the force corresponds to the orthogonal projection of the solid wall. If the balustrade has a lower gap of 50 to 100 mm between the bottom of the panel and the face of the slab to allow runoff water to drain, this escape strip reduces the overall force only slightly: the volume of compressed air at the foot of the balcony generates intense vortices. The metalworker must calculate the complete projected area, including the top rail, the clamping profiles and the area of the posts themselves.

Combination of actions and design of posts and anchorages

The decisive requirement lies in combining the wind load with the horizontal service thrust on the handrail. In a standard residential building, the linear service load applied at the top of the balustrade represents the safety of occupants in the event of involuntary leaning or jostling. According to the calculation rules of SIA 261, the action of the wind and the horizontal load of people are not added arbitrarily at their maximum values without weighting: the check is carried out at the ultimate limit states and serviceability limit states by applying the appropriate combination factors.

For light metalwork, the load case combining the wind pressure acting over the whole height of the glazing and the horizontal outward leaning force is the most demanding situation for the anchorage. The bending moment at the fixing of the post in the concrete slab increases exponentially with the total height of the assembly. Whereas a standard vertical-baluster balustrade 1000 mm high takes only a negligible wind load, a glass panel of the same height accumulates a distributed surface force that generates a major tensile component on the rear anchor of the plate.

The stiffness of the post often requires the choice of a tubular steel section or an aluminium profile with reinforced flange, with a moment of inertia calculated to limit the deflection at the top under the service wind. At the post base, the fixing plate must have a minimum thickness to avoid leverage on the anchors. In the case of a face fixing on the slab edge, the vertical spacing between the two anchor points must provide a sufficient lever arm to contain the pull-out force in the concrete without risk of spalling of the free edge.

Handling defects, excessive deflection and anchorage rework on the construction site

On balconies on upper floors or in a wind corridor, putting a solid balustrade into service sometimes reveals weaknesses that went unnoticed in the technical office. The most common manifestations remain the dynamic flapping of a thin sheet panel, a marked residual deflection at the top of the post after a gust, or the bursting failure of a slab edge when the anchor studs are tightened to torque.

  1. Record the finding and stop installation immediatelyStop the assembly of the section concerned, record the non-conformity in a report with supporting photographs and notify the situation to the site management.
  2. Temporary securing of the open edgeInstall a temporary collective protection firmly tied to the slab to protect the people working on the balcony during the assessment phase.
  3. Recalculation of the support reactionsReview the load path, including the combination of the dynamic wind pressure of the site and the horizontal service thrust, in collaboration with the civil engineer.
  4. Adaptation of the fixingReplace the upper plate anchorage with a threaded rod chemically bonded by injection of high-bond hybrid resin, or switch to a face fixing.

If the problem stems from excessive deformation of the metal structure itself, the metalworker must stiffen the framework without delay. Two technical corrections make it possible to limit the deflection without redoing the whole structure: weld a longitudinal stiffener under the tubular handrail to distribute the wind thrust over the neighbouring posts, or sleeve the inside of the post tubes in the workshop with a solid steel flat bar fitted before reassembly.

Frequently asked questions

How should you react if a laminated glazing vibrates or whistles in wind gusts?

This vibration comes from play in the elastomer seals of the clamps or from an insufficient glass section under dynamic pressure. First check the tightening torque of the clamp screws and the condition of the EPDM packers. If the movements persist, add intermediate clamps at the base or replace the glazing with a thicker build-up with a rigid structural interlayer, after confirmation by the technical office.

Can solid privacy sheets be screwed onto an existing balustrade with balusters?

No, this modification is very risky without a complete structural justification. Adding a sheet turns a permeable open balustrade into an airtight wall that is subject to the maximum sail effect. The wind pressure defined by SIA 261 multiplies the pull-out forces on the existing anchors, which generally were not designed for these combined tensile loads.

What should you do if a slab edge spalls during fixing on top?

Stop installing the post. Spalled concrete cancels the resistance of the anchors' failure cone. Submit a technical change notice to the site management to shift the plate inwards with an adaptation profile, or modify the posts to switch to a side fixing against the slab edge beam using a chemical anchor certified for cracked concrete.

How can a glazed balustrade at an exposed corner on a flat roof terrace be stabilised?

Building corners concentrate strong vortex suction. To guarantee stability without excessively oversizing the individual posts, connect the corner handrails mechanically by a welded and fitted mitre or by a rigid screwed corner connector. This mechanical continuity locks the structure into a spatial box, neutralises the tipping of the panels and distributes the aerodynamic forces between the two orthogonal façades.

Texts and standards cited

  • norme SIA 261Actions on load-bearing structures (definition of wind pressures, exposure factors and load combinations)
  • norme SIA 118General conditions for the execution of construction work (handling of notices of defects, records and order changes)