🧱 CFC 274Balustrades: height, infill and complianceChapter 1 of 10 in the section

Height: the standard minimum, the increased minimum for great heights, and where to measure

This chapter enables you to determine the regulatory height of a metal guardrail according to the free fall height. You will be able to apply the requirements of the SIA 358 standard, locate the level mark on the raw slab with certainty and account for the exact thickness of the finished floor build-up before fabrication starts.

Key takeaways

  • The SIA 358 standard sets the standard minimum guardrail height at a full metre.
  • A fall height of more than twelve metres requires a guardrail of one hundred and ten centimetres.
  • The regulatory measurement must always be taken vertically from the finished walkable surface.
  • Validating the structural work level mark in writing avoids non-conformities at installation.

Determining the regulatory height between a standard landing and a great fall height

In building metalwork, the design of fall protection structures complies with the requirements of the SIA 358 standard. This Swiss technical reference defines the geometry of fixed guardrails in order to prevent personal injury while ensuring comfortable use of walkable areas. The general rule sets a minimum protection height of one hundred centimetres above the accessible area. This one-metre height applies to most terraces, balconies, loggias, access galleries and landings of standard buildings where the difference in level with the receiving ground or the underlying surface creates a hazard.

As soon as the free fall risk exceeds twelve metres in height, the SIA 358 standard requires a reinforced physical barrier. The minimum guardrail height then rises to one hundred and ten centimetres. This threshold is quickly reached on the façades of residential or office buildings, generally from the fourth floor upwards depending on the type of slab-to-slab heights. The vertigo effect and the mechanics of an accidental fall at this height justify this ten-centimetre increase. The metalworker must absolutely identify this change in height on the architect's section drawings before any steel or aluminium is cut in the workshop.

Guardrail height thresholds according to the SIA 358 standard
Free fall heightMinimum guardrail heightTypical location in buildings
Up to 12 metres100 cmBalconies and access galleries on lower floors, raised ground-floor terraces
More than 12 metres110 cmBalconies and roof terraces on upper floors, penthouses, residential towers

Measuring from the finished floor to avoid the screed allowance trap

The classic mistake on construction sites is to fabricate a guardrail by measuring its height from the raw concrete slab. However, the SIA 358 standard expressly states that the protective height is assessed from the finished walkable surface. On a balcony or a waterproofed terrace, the floor build-up often includes a screed to falls, thermal insulation, a bituminous or synthetic membrane, then porcelain stoneware tiles on pedestals or timber decking. This build-up can have a total thickness ranging from forty millimetres to more than two hundred millimetres.

  1. Locating the official level markFind on the concrete walls the one-metre level mark made by the structural work crew with a laser. This mark is the only contractual height reference binding the trades of the finishing work.
  2. Deducting the exact thickness of the floor coveringConsult the approved section details to work out the complete floor build-up: waterproofing, thermal insulation, bedding mortar, adjustable pedestals or finishing self-levelling screed.
  3. Defining the position of the anchor platesFor top-of-slab fixing, increase the height of the metal posts by the thickness of the build-up in order to keep one metre or one hundred and ten centimetres clear above the finished floor.
  4. Recording the execution dimensionsDraw up a written confirmation of the theoretical finished levels before launching the workshop fabrication of the frames, vertical balusters or glass clamps.

When the structure is fixed to the face of the slab edge, assessing the finished level remains just as critical. The top of the handrail must exceed the prescribed final level. A side fixing with slotted holes allows a height adjustment of around ten to fifteen millimetres, but this play can never make up for the complete omission of paving on pedestals. The metalworker who validates the allowances with site management secures their work and prevents costly rework at acceptance of the work.

Taking dimensions and setting the guardrail in relation to the level mark

On a building construction site, guardrail fabrication starts well before the screed is poured or the floor covering is laid. For the metalworker, the only reliable reference during the dimensional survey is the official level mark, generally drawn one metre above the finished floor level by the plasterers or masons. Any dimensions taken directly from the raw concrete slab without checking this mark condemn the structure to geometric non-conformity as soon as the actual floor build-ups differ from the architect's drawings.

The SIA 358 standard requires the protection height to be measured perpendicular to the finished walkable surface. If the waterproofing, thermal insulation or exterior tiling build-up has an unforeseen excess thickness of twenty millimetres compared with the initial allowances, the handrail originally fixed to reach one metre now protects only to ninety-eight centimetres. This shortfall is enough to have the structure rejected at the acceptance inspection. In the workshop, the metalworker must therefore rigorously deduct the exact distance between the installation plane of the plates and the edge on which users lean.

Influence of the floor configuration on the fabrication height of the balustrade
Support configurationSite reference pointItems to deduct or addWorkshop height of the posts
Interior raw slab with liquid screedLevel mark at one metreThickness of insulating screed and tilingFinished floor height plus the clearance under the plate
Balcony with paving slabs on removable pedestalsUpper surface of the ceramic slabHeight of the adjustable pedestals and screed fallsLength under plate adapted to the actual top surface
Waterproofed terrace with gravel or green roofCompacted walkable upper levelWaterproofing upstand and drainage layerRaised post to guarantee the overall dimension
Raw precast concrete staircaseFinished tread nosing with coveringAdhesive thickness and metal nosingStrict vertical alignment from the line of the nosings

Transition to great height: geometry of returns and slab edges

As soon as the drop passes the critical threshold of twelve metres of potential fall, the SIA 358 standard requires a reinforced height of one metre ten. On stepped façades, penthouses or inner courtyards, this transition creates a break in the line that complicates corner connections and end returns. The metalwork site manager must identify precisely the point where the fall goes beyond this threshold in order to build the ten-centimetre step into the layout without creating unintended climbing zones.

  1. Level survey of the natural ground or the impact zoneUse a laser distance meter to measure the exact vertical distance between the finished balcony floor and the lowest landing point at the foot of the structure, including embankments or basement light wells.
  2. Checking for climbable elements below the handrailCheck that no technical upstand, ventilation base or concrete plinth higher than one hundred and fifty millimetres can serve as a step, which would shift the zero point of the measurement.
  3. Drawing the corner connection between different heightsDraw a double post or a smooth linking bracket to connect the one-metre section and the reinforced one-metre-ten section without leaving an opening larger than one hundred millimetres.
  4. Positioning the anchor lugs in the workshopAdjust the vertical spacing of the fixings to absorb the higher pull-out moments generated by the additional lever arm of the great-height version.

For the metalworker, the impact of an unanticipated concrete ledge is immediate: the barrier delivered to the contractual dimensions suddenly becomes too low by the height of this projection. The workshop must absolutely request the final working section from the façade contractors and masons before any frames are fabricated. Where the receiving structure has setbacks or complex slab edges, marking out on a template remains the best assurance that the upper edge of the handrail will strictly comply with the final protection line.

Dealing with height non-conformities at acceptance of the work

On construction sites in French-speaking Switzerland, a non-conforming structure height is generally discovered during the final inspection before handover to the client, or when a thicker floor build-up is laid unexpectedly. If the metalwork workshop has fabricated and installed a 1000 mm guardrail by setting it on the raw concrete slab without deducting the actual thickness of the insulation, the liquid screed and the tiling, the useful height measured from the walkable surface falls short of the requirements of the SIA 358 standard. In this situation, the structure is rejected immediately by site management, because the defect directly affects the safety of the occupants.

  1. Joint inspection record using a laserMeasure the precise dimension between the top of the handrail and the finished floor covering at several points of the balcony or access gallery, in the presence of site management.
  2. Technical study for raising the heightDepending on the geometry of the posts, consider adding a raised handrail using metal brackets, completely replacing the posts or inserting rigid shims under the fixing plates.
  3. Justification of the anchors under the new loadIncreasing the support height increases the lever arm at the shoe or plate. The metalworker must check, or have recalculated, the resistance of the anchors in the slab to withstand the increased overturning moment.

Beyond a fall height of twelve metres, the minimum dimension must be 1100 mm. No negative installation tolerance is accepted by loss adjusters or the courts in the event of personal injury. If on-site adaptation by welding or sleeving proves technically hazardous or visually unacceptable to the architects, dismantling for modification in the workshop is required in order to deliver fully compliant metalwork.

Frequently asked questions

What should be done if the tiler has raised the finished floor by three centimetres compared with the working drawings?

When the finished floor build-up exceeds the contractual allowance, the clear height of the guardrail falls below the 1000 mm required by the SIA 358 standard. The metalworker must immediately draw up a joint inspection record with site management. If the finished level becomes non-compliant through the action of a third party, raising the rail or shimming the plates is covered by a technical and financial addendum validated by the architect.

Can the regulatory height of 1000 mm be measured from a stair step or a parapet wall?

The reference measuring point is always the surface on which a user can place their feet. If a parapet wall or a step has a seat width greater than the tolerated limit, the SIA 358 standard considers this element walkable. The height of 1000 mm, or 1100 mm in the case of great height, must then absolutely be measured vertically from this intermediate support point to prevent unintended climbing.

Does the increased height of 1100 mm apply to an entire building as soon as the fall exceeds twelve metres?

No, the increased height of 1100 mm defined by the SIA 358 standard applies only to the specific zones where the potential fall height exceeds twelve metres. In the same residential or office building, the balcony guardrails on the lower floors up to twelve metres of fall may be made at 1000 mm, while the landings, terraces or loggias above this limit receive guardrails raised to 1100 mm.

Are there any accepted tolerances on the minimum height of a guardrail installed on site?

The SIA 358 standard sets personal protection requirements that allow no undersize execution tolerance. A height of 990 mm for a standard landing is not deemed compliant, even if the general metal construction tolerances allow millimetre deviations. The metalworker must therefore always allow a fabrication margin in the workshop so that the actual dimension on site strictly reaches or exceeds the prescribed 1000 mm or 1100 mm.

Texts and standards cited

  • norme SIA 358Guardrails: minimum protection heights, geometric rules and walkable surfaces