🧱 CFC 281Screed on underfloor heating and floor coveringChapter 8 of 10 in the section

The sensor in the screed: position, replacement conduit, and marking

Directly embedding a thermal sensor in the mortar condemns the control system at the first hardware defect. This chapter details the rules for incorporating the protective conduit within the heated screed. You will learn how to position the tube at mid-thickness between the pipes, ensure its watertightness against cement laitance, record its layout to the millimetre, and organise technical coordination between finishing work trades.

Key takeaways

  • The sensor must always slide freely inside a sealed sleeve emerging into an accessible box.
  • The sealed end must be wedged precisely at an equal distance between two heating pipes in the upper third of the embedding layer.
  • The dimensioned survey of the measuring head guarantees its location after the installation of floor coverings.
  • The screed layer records the condition of the sleeve on the protocol prior to any mortar installation.

Altimetric layout and mechanical installation of the protective sleeve

Incorporating a floor temperature sensor must never be done by direct embedding in the screed mortar. A sensor embedded without the possibility of withdrawal necessitates destructive core drilling or the outright abandonment of the control system at the first malfunction of the sensitive element. The screed layer must require the prior installation of a continuous, watertight sleeve with a smooth interior, which ensures the effortless replacement of the sensor from the control cabinet or wall thermostat. Thermal positioning requires that the measuring head captures a representative value of the heated mass, without being distorted by the immediate contact of a heat-transfer pipe. The end of the sleeve must therefore be strictly clamped at an equal distance between two coils of the underfloor heating, parallel to the pipes, over a straight length of at least fifty centimetres.

  1. Checking the bending radiusCheck the transition between the vertical wall and the floor. The bending radius of the conduit must exceed twenty centimetres to prevent any crushing or sharp bend that would prevent the passage of the sensor.
  2. Altimetric fastening on the insulationSecurely fasten the conduit to the mesh or insulation using appropriate clips. The end must be located at the level of the neutral fibre of the screed, just above the plane of the heating pipes.
  3. Sealing and pull testCheck the installation of the watertight plug at the end of the tube. Perform a passage test using a flexible drawing wire to confirm the absence of pinching before authorising pouring.
Installation tolerances and geometric requirements for the sensor sleeve
Installation parameterRequired valueConsequence of a defect
Distance to heating pipesExact centring between two coilsErratic thermal measurement influenced by the supply or return
Wall bending radius200 mm minimumMechanical jamming of the cable during a replacement attempt
Height in the screedIn the upper third or at mid-thicknessPoor thermal representativeness and risk of surface contact

Geometric marking, as-built plan, and coordination on the construction site

Preserving the installation requires rigorous traceability from the moment the conduits are installed. Once the screed mortar has been leveled or poured, the surface completely conceals the technical networks. The sensitive end of the conduit must be recorded by dimensioned triangulation, referenced to two corners of load-bearing walls or fixed door frames in the room. This exact measurement is reported on the as-built plans of the completed structure. This survey prevents any subsequent drilling when fixing door stops, light partition rails, or threshold bars by other finishing work trades. It also allows for targeted intervention in the event of accidental crushing occurring during pouring phases.

Screed as-built plan
Contractual graphic document drawn up upon completion of the work, recording the exact location of expansion joints, pipe penetrations, and sensor sleeves embedded in the screed.
  • Joint verification of the sleeve fastening with the heating installer prior to site delivery.
  • Visual inspection during pouring to ensure that carts, pumping hoses, or power floats do not displace the conduit.
  • Transmission of the as-built report to the site management for integration into the construction file.
  • Express mention in the heating-up protocol of the operating condition of the sensor conduit.

Coordination on the construction site is the guarantor of the durability of the measuring system. The screed layer cannot be held responsible for the failure of a sensor if the conduit has not been installed in accordance with good practice by the competent technical company. On the other hand, the duty of diligence requires reporting any obvious anomaly, such as a floating or unblocked conduit, before starting mixing or pumping. The joint signature of an interface control slip prior to pouring protects all partners against disputes relating to underfloor heating.

Guarantee of future replacement: conduit geometry and protection against laitance

A temperature sensor embedded directly into a screed matrix without a protective casing constitutes a point of no return for the thermal installation. As soon as a measurement drift or a short circuit of the sensitive element occurs, the impossibility of extracting the measuring cell condemns the fine control of the room or forces destructive core drilling. For the structure to remain durable, the screed layer must ensure, before any mortar is poured, that the sensor rests in a continuous, watertight, and mechanically stable sleeve tube, allowing the removal and insertion of a new sensor from the wall box or manifold.

The choice of the protective tube directly determines the usability of the installation. Standard small-diameter corrugated conduits frequently create internal sharp edges at bends, against which the rigid head of the sensor hits during insertion attempts. The use of a semi-rigid conduit with a smooth inner wall, or a specially dimensioned corrugated conduit, avoids excessive cable friction. The terminal end of the conduit, housed in the heart of the screed, must imperatively be closed by a sealed hermetic plug or a heat-shrinkable sleeve. Basic sealing with adhesive tape systematically yields under the hydrostatic pressure of the fluid mortar or under the vibrating action of the screeding rule, resulting in the penetration of laitance that permanently cements the passage.

  1. Checking the altimetric level within the thicknessThe sensor conduit must be fixed at the level of the median plane of the total thickness of the screed, or at an equal distance between the top of the heating pipes and the upper face of the rough screed. Under no circumstances must it rest in direct contact with a heating pipe, which would immediately distort the control measurement by picking up the temperature of the heat-transfer fluid rather than the inertia of the mineral mass.
  2. Wedges and mechanical anchorageThe sleeve must be solidly secured to the reinforcing mesh or insulation fixing clips using saddles or clamping collars every 500 mm. The buoyancy force exerted by a self-levelling fluid screed is sufficient to lift a poorly clamped sleeve, causing it to rise flush beneath the finished surface, where it weakens the mechanical strength of the embedding layer.
  3. Preliminary sliding testBefore authorising pouring, the electrical or heating installer must pass a drawing wire or test sensor along the entire length of the route, from the control panel to the terminal plug, to validate the absence of pinching or too tight a bend.

Inter-trade coordination, interface report, and durable marking

The integration of room and thermal limitation sensors in the screed requires a rigorous delimitation of services between the heating fitter, the electrical installer, and the screed layer. According to standard coordination rules on Swiss building sites, the supply, layout, and fixing of the conduit are the responsibility of the technical trades. The screed layer, for their part, assumes responsibility for the visual inspection of the embedding layer, compliance with the nominal thickness above the sleeve, and the preservation of its mechanical integrity during the pumping, leveling, and floating phases of the mortar.

Interface responsibility matrix for the control sensor sleeve
Intervention stepResponsible tradeObject of the joint checkExpected deliverable
Installation and fixing of the conduitHeating engineer / ElectricianBending radius, equidistant spacing between coils, anchorage on insulationInstallation self-control sheet
Geometric surveySite management / Heating engineerTriangulated dimensions relative to finished wall cornersDimensioned as-built plan
Acceptance of the substrateScreed layerAbsence of pinching, sealing of the terminal plug, firm retentionVisa on pouring protocol
Pouring of the screedScreed layerMaintenance of altimetry under the flow, protection against tool impactsEntry in the site diary

The physical marking of the end of the conduit must not disappear during the installation of hard or flexible floor coverings. While the as-built plan attached to the construction file records the metric distances relative to the masonry walls, an in-situ marking remains essential for emergency interventions. On sites requiring total traceability, the exact position of the measuring bulb is recorded by photographic triangulation before embedding, supplemented by a discreet but indelible marking at the thermal distribution manifold indicating the loop and the room controlled by the corresponding sensor.

Claims and disputes: what to do in the event of a defective or inaccessible conduit?

When the heating engineer or electrician notes that a thermal sensor refuses to slide or that the protective conduit has been crushed, the construction site faces heavy remedial work. A corrugated conduit deformed by the passage of workers or clogged by self-levelling grout makes replacement impossible without destroying the floor assembly. The screed layer who works on a poorly secured, open, or badly positioned routing runs the risk of bearing responsibility if they have not issued any prior remarks. In accordance with good practice and the recommendations of SIA 251 standard and SIA 118 standard, the contractor exercises their duty to notify and reports in writing any visible anomaly before the start of pumping.

  1. Recording the blocking distanceInsert a graduated electrician's fish tape from the wall control box to the stopping point to determine the exact length of the usable section.
  2. Non-destructive location of the obstacleCross-reference the metric measurement with the as-built plan or use a thermal camera during the heating phase to delineate the precise area of the blockage in the room.
  3. Surgical clearance and sleevingLocally open the screed using a flat chisel and industrial vacuum cleaner while avoiding the heating pipes, cut out the crushed section, insert a watertight smooth sleeve, and seal with a reactive resin mortar.

If the conduit proves untraceable, embedded without marking, or irremediably crushed under a dense underfloor heating circuit, all blind mechanical probing is prohibited to avoid perforating the pressurized coils. Site management must record the failure and order a fallback solution validated by the HVAC engineering firm. The system then switches to pure room measurement or surface sensors concealed under skirting boards, which modifies the control parameters but preserves the overall integrity of the structure according to SIA 251 standard.

Frequently asked questions

Why is it forbidden to directly embed a sensor without a sleeve in the screed?

A temperature sensor sealed bare into the mortar becomes impossible to replace in the event of a short circuit or drift of the electronic component. Its lifespan is often shorter than that of the building. Without a continuous protective sleeve emerging into an accessible box, the slightest failure requires demolishing the tiling or permanently abandoning the slab control system, turning a simple equipment replacement into a costly claim for the structure.

At what exact depth in the screed must the sensor head be located?

The sleeve must position the sensitive element in the upper third of the floating screed, at the geometric mid-distance between two underfloor heating pipes. This positioning prevents the measurement from being distorted by the direct radiation of the heat-transfer fluid and faithfully reflects the heat transmitted towards the final covering. The terminal end of the conduit must be rigidly clamped so as not to float during pouring or sink against the underlying thermal insulation.

Who must supply and install the marking plan for the conduit end?

The sanitary or electrical installer installs the conduit and must imperatively provide the precise survey of its dimensioned layout relative to the raw walls. The screed layer checks for the presence of these markers before pouring their mortar. This as-built document is handed over to the site management to be recorded in the construction file, guaranteeing the tiler or parquet layer that they will not drill into the conduit during subsequent floor work.

How to ensure that the screed grout does not penetrate the sleeve?

The protective tube must feature a smooth inner wall, without fragile intermediate joints, and end with a sealed factory-crimped or welded closed tip. The use of simple site adhesive tape is prohibited, as the moisture under pressure from the liquid screed dissolves adhesives and causes laitance infiltrations. The contractor checks this mechanical watertightness at the time of their preliminary inspection prior to the implementation of the mortar.

Texts and standards cited

  • SIA 118General conditions for the execution of construction work (duty to notify and defect management)
  • SIA 251Floating screeds inside buildings (installation rules, interfaces, and tolerances)